DIY Home Improvement Forum banner

Discussions Showcase Albums Media Media Comments Tags Marketplace

1-7 of 7 Results
  1. Electrical
    Have an existing generator subpanel with interlock that supplies power from the mains panel OR a generator, never both. The subpanel was installed strictly in accordance with instructions and uses 6 AWG for hots and neutral. Want to use a Victron inverter/charger (meets the definition of an...
  2. Electrical
    I'm in Texas and we just went through the 'winter vortex' storm that took out power, water and had everyone scrambling. I have 2 generators (each 10k/8kW). They can't be paralleled because they are not inverter gens. But I've been reading some prior posts about the possibility of running 2...
  3. Electrical
    Hey all, I'm looking for a generator interlock kit for a 100A GE tsm1610cfcu panel (picture attached below). I'm not finding the right kit on either of the websites I'm familiar with (GenInterlock.com & InterlockKit.com). The only one I've found that looks like it might work is this kit on...
  4. Electrical
    The Internet has given me every possible answer to this question, so I turn to you, the experts. I have a Westinghouse WGen 7500 Watt portable generator. It is neutral bonded. I am connecting it to a Reliance 306 transfer switch. (Side question...electricians on the internet seem to treat...
  5. Electrical
    Hey everyone! I have a Cutler Hammer Meter/Panel Outdoor combo that feeds my interior panel with 200 AMP service. As you can see, it has the main breaker, and then two breakers in use, one for a GFCI outlet directly below the panel, and another for the RainBird Irrigation Controller, also...
  6. Electrical
    I have an idea for my installation of a generator interlock at my cottage. I've wanted to install a transfer system and get a bigger panel, so this should solve my problems. The only issue I've thought of with the interlock is: How will I know if the powers gone back on? So I thought, why not...
  7. Electrical
    I installed a generator interlock kit on a 100AMP HO panel box. all circuits run fine using utility power. when I switch to Generator power all circuits work fine except for the sump pump. I ran 12/2 from the other end of the house where the sump pump is, to the main panel to a 20amp breaker. it...
1-7 of 7 Results
Top