1-11 of 11 Results
  1. HVAC
    The other day I noticed that hot air was coming out of my vents when I had the A/C running. I went and looked at the condenser and the compressor was running but the fan was not and the fan motor was very hot. After doing some studying, I replace the cap and turned the A/C back on but the fan...
  2. HVAC
    I just replaced my condenser fan motor because the bearings were shot in my old one. My unit is a Keeprite KSSD 19-36, probably around 25 years old. The old motor had 4 wires, red, black, brown and white. The new motor's wires are yellow, black, brown, and brown/white. After I installed the...
  3. HVAC
    Hello, my condenser fan is not coming on and I cannot seem to find the same motor. The motor is a GE 5kcp39bg S457S. 1/10 hp, 208-230V, 1100RPM 60HZ. The capacitor does not have any numbers listed on it, but it has 3 posts coming out of the top. The unit is a Gibson GS3BA-024KA (2ton) I...
  4. HVAC
    Fan Motor locked up last night, nothing done could get it to stay running. :( So we found a DIY HVAC supply today, got a new fan motor, got instructions how to wire it, did as told (brown and brown to cap / white, red, black to line) Almost POSITIVE that its wired correctly, BUT it keeps...
  5. Electrical
    I am having to replace the condenser fan motor due to bad bearing/burn out. Here's where i am in the process: Got the new motor. The old one had 3 wires, red, brown and black. The new one has brown, brown/white stripes, black, and white. I also got a new run capacitor. This is NOT a dual...
  6. HVAC
    So i have to replace the condenser fan motor, it wont spin freely and it looks like the bearings are worn out. The old motor says it is a 1/4hp with 2.2 FLA(full load amps), 208/230V, PH1. It does not say what the rpm's are and neither does the fan blade. So i found on Grainger two motors that...
  7. HVAC
    I recently changed my Condenser Fan Motor as the other one locked up right before vacation. The motor was a 1/10 HP and the only motor I could find locally with the same RPM was a 1/2 HP. The old fan was .7 Amps and thew new one is 3.5-4.0. 1--What if any effects will this cause on my AC...
  8. HVAC
    Hi all, I got a situation, 2 family house with 2 HVACs, one is 2 Ton the other 2.5 ton The condenser fan on the 2.5 ton unit went bad after 3 years. So I took the fan from the 2 ton unit and put it to the 2.5 ton unit. Looks to be running fine - 2nd day However now that I want to get a new fan I...
  9. HVAC
    My 5 Ton AC condenser worked well last year but it is not working this year. Both compressor and condenser fan are not running. The situation is below: 1. There is a AC power 110V between 2 hot lines on the contactor input terminals before turning on the AC. But this power is gone after...
  10. HVAC
    When I got my AC tune-up done this spring, second unit condenser fan wasn't running. Compressor was running. Little push with a wooden stick to fan made fan started but very slow speed. Tech advised me to get motor replaced as Capacitor is OK. His quote was very high so, I decided to myself. I...
  11. HVAC
    I just replaced the condenser fan motor and capacitor (orig AO Smith F48P99A76, new Diversitech WG840204 - same specs) in my Goodman outside unit. The original fan stopped turning, had high resistance between leads (700 - 1300 ohms), hard to turn by hand. The orig fan had 3 leads, one to the...