Old 07-17-2010, 11:09 PM   #16
UAW SKILLED TRADES
 
Stubbie's Avatar
 
Join Date: Jan 2007
Location: Kansas
Posts: 5,341
Rewards Points: 2,652
Default


Proby

I don't think you understand what I'm suggesting by using a 15 amp MWBC but the OP has already ran the #12 from the panel ... so Jims suggestion is likely his best bet.
__________________
" One nice thing about the NEC articles ... you have lots of choices"

Stubbie
Stubbie is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 07-17-2010, 11:18 PM   #17
Electrician
 
Proby's Avatar
 
Join Date: Jul 2010
Location: NJ
Posts: 818
Rewards Points: 500
Default


Quote:
Originally Posted by Stubbie View Post
Proby

I don't think you understand what I'm suggesting by using a 15 amp MWBC
I understand what you are saying, but if we are trying to be code compliant here, 2 15A circuits will not fill in for a required 20A circuit.
Proby is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 07-18-2010, 12:39 AM   #18
UAW SKILLED TRADES
 
Stubbie's Avatar
 
Join Date: Jan 2007
Location: Kansas
Posts: 5,341
Rewards Points: 2,652
Default


The issue is are we thinking outside the box and violating the NEC as to following manufacturers instructions which are calling for a 20 amp dedicated circuit to the unit. The other problem is we have fixed space heating which requires a continuous load calculation for the heater. All this considered requires #12 conductors ... and protection according to 240.4D.

So I concur it would not be code compliant to use a 15 amp Multiwire branch circuit.
__________________
" One nice thing about the NEC articles ... you have lots of choices"

Stubbie
Stubbie is offline   Reply With Quote
Sponsored Links
Advertisement
 
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Size and type of entrance wire for 200A? Beemer533 Electrical 7 03-15-2010 10:54 PM
HALP! Master/Remote Dimmer troubles! Confuserated Electrical 9 02-12-2010 03:30 PM
Size of Wire & type of wire agman Electrical 6 11-10-2009 08:13 PM
Wire size for Central Air mwtuck HVAC 2 12-01-2006 05:06 PM
wire size wire to 10kw furnace? lochcarron Electrical 1 04-10-2005 07:43 PM




Top of Page | View New Posts