Old 07-29-2010, 02:01 PM   #16
Electrician
 
Proby's Avatar
 
Join Date: Jul 2010
Location: NJ
Posts: 818
Rewards Points: 500
Default


Quote:
Originally Posted by kboothe View Post
Thanks!

one last question, you wrote:
You can't have current running down one cable and coming back thru a second, whether it be a hot and neutral or a switch leg.

Why is this not allowed (current running from one cable and back a different cable)?

NEC 300.3 Conductors
(B) Conductors of the Same Circuit. All conductors of the same circuit and, where used, the grounded conductor and all equipment grounding conductors and bonding conductors shall be contained within the same raceway, auxiliary gutter, cable tray, cablebus assembly, trench, cable, or cord, unless otherwise permitted in accordance with 300.3(B)(1) through (4).
Its the fundamental requirement of this section that single conductors shall be grouped together to mitigate the parasitic effects of magnetic and electric fields. One of the ways to achieve grouping is by using conduit/raceways etc. If a raceway etc is used, all conductors of the circuit must be contained therein.


There are acceptations when using romex in plastic boxes, that will relieve the heating in metal boxes. But it's still not good practice, you are introducing unwanted electrical and magnetic fields into your home.
__________________
Anything fun is either illegal, immoral, or fattening.
Proby is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 07-29-2010, 02:18 PM   #17
Newbie
 
Join Date: Jul 2010
Posts: 8
Rewards Points: 10
Default


Thanks!
kboothe is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 07-29-2010, 04:27 PM   #18
Member
 
57_Hemi's Avatar
 
Join Date: Jul 2010
Location: TORONTO CANADA
Posts: 81
Rewards Points: 75
Default


Cool !!!!!

Last edited by 57_Hemi; 07-29-2010 at 04:28 PM. Reason: prob solved
57_Hemi is offline   Reply With Quote
Sponsored Links
Advertisement
 
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
How many wires in Romex v. extension cord? Leah Frances Electrical 31 06-02-2010 10:24 PM
two romex wires in 3/4" conduit ugabulldog Electrical 12 05-24-2010 01:40 PM
Can't find the wires! brianmarsh Home Theater 2 01-24-2010 07:11 AM
Unfused connectors MELTED House wires WHAT TO DO??? jamiedolan Electrical 63 02-12-2009 06:01 PM
Use of unsheathed Romex NM-B wires in conduit? WoodworkerDave Electrical 10 09-29-2008 05:57 PM




Top of Page | View New Posts