Old 02-23-2019, 08:40 AM   #16
Member
 
Join Date: Jan 2019
Location: Houston, TX
Posts: 69
Rewards Points: 126
Default

Re: Sch 40 vs 80 for Underground


Quote:
Originally Posted by curiousB View Post
No wide sweep bends for the 90s underground. For 2 its a bend radius of 10 or more or youll never be able to pull cable. Use LB fitting at sides of buildings.
Got it, will get 90 degree bends and put the LBs at the sides of buildings. Do I also need an LB at the main panel side or just the subpanel side. I was thinking just the subpanel side b/c that is the only place where the wiring needs to go inside (my main panel is already outside)

Quote:
Originally Posted by rjniles View Post
Not sure where you are getting these numbers but with THWN conductors the minimum size with Sch 80 would be 1.25". Fill cannot exceed 40%.

Unless you have a typo and mean 1.5"
I think he meant 1.5" because my original question was about 1.5"
spacefrog is offline   Reply With Quote
Sponsored Links
Advertisement
 
Reply

Tags
electrical


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off





Top of Page | View New Posts