tonepaq 05-21-2017 05:21 PM

Proper junction box for addition
 
Working on a house that had an addition put on in the mid 90's. The new service panel is located in the basement of the addition. Looks like they tied in the old part of the house in an existing box with electrical tape and caps :vs_worry:

What would be a proper box to use to junction all these wires properly?

http://i67.tinypic.com/ie47ww.jpg
http://i64.tinypic.com/24fjjba.jpg
http://i67.tinypic.com/ie47ww.jpg

joed 05-21-2017 05:27 PM

Re: Proper junction box for addition
 
That box is fine if it has a cover.

tonepaq 05-21-2017 05:40 PM

Re: Proper junction box for addition
 
Quote:

Originally Posted by joed (Post 4268993)
That box is fine if it has a cover.

Whats the proper connections for the heavier gauge wires in there? Im guessing the electrical tape isn't up to code?

joed 05-21-2017 07:56 PM

Re: Proper junction box for addition
 
The only problem I see i the large ground that is not connected and may not need to be if it goes to the rods. That connection should be in the main panel.

Oso954 05-21-2017 07:59 PM

Re: Proper junction box for addition
 
Quote:

Originally Posted by tonepaq (Post 4269065)
Whats the proper connections for the heavier gauge wires in there? Im guessing the electrical tape isn't up to code?

The heavy wires at the top have a split bolt connection that is taped to insulate the bolt/connection.

Jim Port 05-21-2017 08:39 PM

Re: Proper junction box for addition
 
Anyone think the ground is touching the aluminum in the one lug?

afjes2015 05-22-2017 07:37 AM

Re: Proper junction box for addition
 
Something else that caught my attention in this "jbox" set up.
The incoming 2 legs and braided neutral on the left top side. The neutral braid is in a lug and the outgoing power there are two legs going out but with what seems to be a bare solid copper wire (in the lug with the braided neutral conductor) being used as the neutral going out instead of a braided or proper conductor to be used as a neutral.