Clarification on PVC Conduit Depth


Alright,

Everywhere I have read says PVC conduit must be atleast 18 inches deep at the top of the PVC pipe... but I had a electrician come over and tell me it has now changed in the 2008 NEC to 24 inches... can anyone confirm or clarify? I am looking in the NEC I just figured someone that knows it better would know exactly where it is in the NEC
joshvette001 is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 05-09-2010, 03:45 PM   #2
Inspector/Instructor
 
codeone's Avatar
 
Join Date: Dec 2009
Location: NC
Posts: 369
Rewards Points: 250
Default


Depends on the application!
Is it going to be at a residence, under concrete, under a building, under a driveway, encased in concrete, etc?
codeone is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 05-09-2010, 04:20 PM   #3
Inspector/Instructor
 
codeone's Avatar
 
Join Date: Dec 2009
Location: NC
Posts: 369
Rewards Points: 250
Default


Maybe this will help.
Attached Images
 
codeone is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 05-09-2010, 08:00 PM   #4
Member
 
Join Date: Sep 2008
Location: SoCal
Posts: 1,802
Rewards Points: 1,016
Default


Ask when you pull your permit to ensure you get the proper answer for your locale and application. To my detached garage/workshop this past year was 18" over the conduit - so dug to a 20" trench depth.
vsheetz is offline   Reply With Quote
Old 05-09-2010, 08:09 PM   #5
liscenced electrician
 
Join Date: Jul 2008
Location: Oregon coast
Posts: 1,013
Rewards Points: 540
Default


most applications would be 18 inches deep, hasn't changed



i dig mine as low as i can. if im using equipment, ill dig it to 3 feet
jimmy21 is offline   Reply With Quote
Old 05-09-2010, 08:44 PM   #6
Licensed Electrical Cont.
 
Speedy Petey's Avatar
 
Join Date: Feb 2004
Location: NY State
Posts: 7,828
Rewards Points: 2,006
Default


Anything one or two family residential is 18" at the most. Even driveways.
Speedy Petey is offline   Reply With Quote
Sponsored Links
Advertisement
 
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
PVC conduit - custom offset or bending tns1 Electrical 25 08-29-2011 05:56 PM
Water in conduit MYSTERY feign3 Electrical 4 03-14-2010 08:17 AM
Chicago Conduit Rules Wrigleyville Electrical 6 01-28-2010 06:49 PM
Sheathing/siding around conduit destroyer427 Building & Construction 1 10-20-2009 05:25 PM
Sealing conduit coming into house encased with waterline pacamaroman Plumbing 3 06-18-2009 08:48 AM




Top of Page | View New Posts