Question

Side wall vent kit for 2-pipe furnace


In my Goodman furnace manual it describes how a "side wall vent kit" can be used instead of the standard 2-pipe termination options. They seem like a much easier and aesthetically pleasing option than the standard pipe terminations. Has anybody had any issue with these kits?

The reason I ask is the kits have the intake and flue pipes very close together, and it seems to contradict the minimum clearances required when just running the pipes out normally. Goodman want a 12" clearance between the intake and flue pipes, and in the kit they're RIGHT near each other, albeit the intake is sucking from behind the face plate while the vent is blowing out through the front of it - still, it seems very close.

Any thoughts appreciated, thanks.
Attached Thumbnails
Side wall vent kit for 2-pipe furnace-selection_004.png  
__________________
On the one ton temple bell
a moon-moth, folded into sleep

Last edited by tom_poconos; 05-12-2020 at 10:06 AM.
tom_poconos is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 05-12-2020, 10:37 AM   #2
Member
 
Join Date: Jun 2018
Location: Colorado
Posts: 519
Rewards Points: 894
Default

Re: Side wall vent kit for 2-pipe furnace


I've used many. No problems at all.
57TinkerMan is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 05-12-2020, 11:06 AM   #3
Member
 
Join Date: Nov 2014
Posts: 5,836
Rewards Points: 716
Default

Re: Side wall vent kit for 2-pipe furnace


Just a concentric vent kit. Very popular. Very widely used.
roughneck is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 05-12-2020, 05:34 PM   #4
Member
 
tom_poconos's Avatar
 
Join Date: Nov 2017
Location: Philly
Posts: 262
Rewards Points: 524
Default

Re: Side wall vent kit for 2-pipe furnace


Good to know. I just thought they contradicted the minimum distances in the standard termination illustrations and might lead to performance/efficiency issues.
__________________
On the one ton temple bell
a moon-moth, folded into sleep
tom_poconos is offline   Reply With Quote
Sponsored Links
Advertisement
 
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off





Top of Page | View New Posts