vented vinyl soffit?


I'm trying to calculate how how much venting I need to balance my ridge vent.

These are the vinyl soffit panels I'm using (as well as the solid type):
http://www.homedepot.com/h_d1/N-5yc1v/R-202666273/h_d2/ProductDisplay?catalogId=10053&langId=-1&keyword=vented+vinyl+soffit&storeId=10051#specif ications

My entire soffit is open to the roof deck. The only covering will be these vinyl soffit coverings. However, there is no NVFA rating on these vented soffit panels. Does anyone have a clue as to what it may be?

Similar homes in my neighborhood have every third soffit panel vented, others have every other, and other homes have every soffit panel vented.

Any help?

novaguy is offline   Reply With Quote
Old 12-09-2012, 03:16 PM   #2
Roofmaster
 
Join Date: Oct 2012
Location: Maryland
Posts: 3,668
Rewards Points: 2,094
Default

vented vinyl soffit?


Go all vented. Your soffit venting gets blocked up with atmospheric dirt, pollen etc. etc. in short order, and all your calcs go bogus

jagans is offline   Reply With Quote
Old 12-09-2012, 03:19 PM   #3
Newbie
 
Join Date: Nov 2012
Posts: 13
Rewards Points: 10
Default

vented vinyl soffit?


From what I've read so far, it looks like the vented soffits with 1/8" holes spaced 1/2" on center give about 6 nvfa per square foot of soffit.
novaguy is offline   Reply With Quote
Old 12-09-2012, 03:20 PM   #4
Registered User
 
Join Date: Mar 2009
Posts: 9,967
Rewards Points: 2,000
Default

vented vinyl soffit?


The triple 4" are 4.65 sq.in. NFVA per foot deep. Most ridge vents are 18 NFVA (good ones- to meet minimum 1/150) or 9NFVA per simple gable house side. You need a 2' deep soffit. Problem with your choice (design flaw) is dust/dirt moving through the very small holes deposit there from moisture in the air and restrict the NFVA to very little. Also, the best location for optimum air pressure intake is right next to the fascia board, not near the house; pp. 615-617; http://books.google.com/books?id=Z8a...0vents&f=false

Gary
__________________
If any ads are present in my answer above, I do not condone/support/use the product or services listed, they are there against my permission.
Gary in WA is offline   Reply With Quote
Old 12-09-2012, 03:39 PM   #5
Newbie
 
Join Date: Nov 2012
Posts: 13
Rewards Points: 10
Default

vented vinyl soffit?


Wow, I'm more screwed up than I thought. I only have a 12" soffit on my garage. Looks like I need to get the 16x4 under-eave soffit vents. Each one (according to the home depot website) is 26 NVFA? That seems too high.

So, if I use the ridge vent with 18 NVFA, and I have continuous soffit venting along both eaves with 26 NVFA, I should be good, yes? Absolute no chance of ridge reversal there!

EDIT: I think I'll just order the SV202 vent as recommended in the book (great book, btw!) and that will give me a more balanced airflow between the 18NVFA ridge vent, and the 9NVFA SV202 on both eaves. Thanks again for the awesome help, GBR. I owe you a case of beer.

Last edited by novaguy; 12-09-2012 at 03:56 PM.
novaguy is offline   Reply With Quote
Old 12-09-2012, 04:21 PM   #6
Registered User
 
Join Date: Mar 2009
Posts: 9,967
Rewards Points: 2,000
Default

vented vinyl soffit?


Lol, H.D. info can confuse one, like watching TOH for DIY advice; http://www.airvent.com/pdf/installat...it-install.pdf 9 NFVA per foot is perfect. I owned/drove a '67 Nova wagon for about 12 years, had it painted before I sold it for 1/2 again more than I paid initially, nice car, solid.

Gary

__________________
If any ads are present in my answer above, I do not condone/support/use the product or services listed, they are there against my permission.
Gary in WA is offline   Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Vinyl Perf Soffit over Wood - No Vents nickelshine Roofing/Siding 18 05-29-2012 10:12 AM
need advice installing soffit vents in vinyl siding tspoon84 Roofing/Siding 4 01-05-2012 10:20 PM
vinyl Siding / Soffit Question J S Machine Building & Construction 42 04-18-2011 11:11 PM
Vinyl soffit and fascia msyv Building & Construction 7 09-13-2009 11:21 PM
Vinyl Soffit man117 Building & Construction 4 11-11-2008 06:53 PM




Top of Page | View New Posts

Copyright © 2003-2014 Escalate Media. All Rights Reserved.