Forums | Home Repair | Home Improvement | Painting | Interior Decorating | Remodeling | Landscaping


Go Back   DIY Chatroom Home Improvement Forum > Home Improvement > Roofing/Siding

CLICK HERE AND JOIN OUR COMMUNITY TODAY...IT'S FREE!

Reply
 
Thread Tools Search this Thread Display Modes
Old 12-09-2012, 01:39 PM   #1
Newbie
 
Join Date: Nov 2012
Posts: 13
Share |
Default

vented vinyl soffit?


I'm trying to calculate how how much venting I need to balance my ridge vent.

These are the vinyl soffit panels I'm using (as well as the solid type):
http://www.homedepot.com/h_d1/N-5yc1v/R-202666273/h_d2/ProductDisplay?catalogId=10053&langId=-1&keyword=vented+vinyl+soffit&storeId=10051#specif ications

My entire soffit is open to the roof deck. The only covering will be these vinyl soffit coverings. However, there is no NVFA rating on these vented soffit panels. Does anyone have a clue as to what it may be?

Similar homes in my neighborhood have every third soffit panel vented, others have every other, and other homes have every soffit panel vented.

Any help?
novaguy is offline   Reply With Quote
Old 12-09-2012, 02:16 PM   #2
Roofmaster
 
Join Date: Oct 2012
Location: Maryland
Posts: 3,406
Default

vented vinyl soffit?


Go all vented. Your soffit venting gets blocked up with atmospheric dirt, pollen etc. etc. in short order, and all your calcs go bogus
jagans is offline   Reply With Quote
Old 12-09-2012, 02:19 PM   #3
Newbie
 
Join Date: Nov 2012
Posts: 13
Default

vented vinyl soffit?


From what I've read so far, it looks like the vented soffits with 1/8" holes spaced 1/2" on center give about 6 nvfa per square foot of soffit.
novaguy is offline   Reply With Quote
Old 12-09-2012, 02:20 PM   #4
Registered User
 
Join Date: Mar 2009
Posts: 9,886
Default

vented vinyl soffit?


The triple 4" are 4.65 sq.in. NFVA per foot deep. Most ridge vents are 18 NFVA (good ones- to meet minimum 1/150) or 9NFVA per simple gable house side. You need a 2' deep soffit. Problem with your choice (design flaw) is dust/dirt moving through the very small holes deposit there from moisture in the air and restrict the NFVA to very little. Also, the best location for optimum air pressure intake is right next to the fascia board, not near the house; pp. 615-617; http://books.google.com/books?id=Z8a...0vents&f=false

Gary
__________________
Clothes taking longer to dry?
Clean the dryer screen in HOT water if using fabric softener sheets.
They leave a residue that impedes air-flow, costing you money.
Clean the ducting in the last six months? 17,000 dryer fires annually!
Gary in WA is offline   Reply With Quote
Old 12-09-2012, 02:39 PM   #5
Newbie
 
Join Date: Nov 2012
Posts: 13
Default

vented vinyl soffit?


Wow, I'm more screwed up than I thought. I only have a 12" soffit on my garage. Looks like I need to get the 16x4 under-eave soffit vents. Each one (according to the home depot website) is 26 NVFA? That seems too high.

So, if I use the ridge vent with 18 NVFA, and I have continuous soffit venting along both eaves with 26 NVFA, I should be good, yes? Absolute no chance of ridge reversal there!

EDIT: I think I'll just order the SV202 vent as recommended in the book (great book, btw!) and that will give me a more balanced airflow between the 18NVFA ridge vent, and the 9NVFA SV202 on both eaves. Thanks again for the awesome help, GBR. I owe you a case of beer.

Last edited by novaguy; 12-09-2012 at 02:56 PM.
novaguy is offline   Reply With Quote
Old 12-09-2012, 03:21 PM   #6
Registered User
 
Join Date: Mar 2009
Posts: 9,886
Default

vented vinyl soffit?


Lol, H.D. info can confuse one, like watching TOH for DIY advice; http://www.airvent.com/pdf/installat...it-install.pdf 9 NFVA per foot is perfect. I owned/drove a '67 Nova wagon for about 12 years, had it painted before I sold it for 1/2 again more than I paid initially, nice car, solid.

Gary
__________________
Clothes taking longer to dry?
Clean the dryer screen in HOT water if using fabric softener sheets.
They leave a residue that impedes air-flow, costing you money.
Clean the ducting in the last six months? 17,000 dryer fires annually!
Gary in WA is offline   Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Vinyl Perf Soffit over Wood - No Vents nickelshine Roofing/Siding 18 05-29-2012 09:12 AM
need advice installing soffit vents in vinyl siding tspoon84 Roofing/Siding 4 01-05-2012 09:20 PM
vinyl Siding / Soffit Question J S Machine Building & Construction 42 04-18-2011 10:11 PM
Vinyl soffit and fascia msyv Building & Construction 7 09-13-2009 10:21 PM
Vinyl Soffit man117 Building & Construction 4 11-11-2008 05:53 PM




Top of Page | View New Posts

Copyright © 2003-2014 Escalate Media. All Rights Reserved.