Roof Blowing off


our home was built new in 09/2001. Since the first winter we have been loosing shingles every time the winds go over 30mph. The shingles are IKO DHB Cambridge 25 yr. I noted that the clear plastic strip over the adhesive is still present on the ones that have blown off. The shingles were stapled on the home for some reason instead of nailed. We have even lost shingles after they were repaired by the contractor. I also noted that they did not use a common tar paper underneath the shingles. It looks like some kind of recycled paper and it is light brown in color, so you know what that is?
I have also noted that when the wind blows I can see A LOT of shingle ends coming up in the breeze. I am very concerned. Can you advise?
Thanks Don.

Advertisement

  Reply With Quote
Old 03-08-2004, 11:24 PM   #2
Member
 
Grumpy's Avatar
 
Join Date: Dec 2003
Location: Chicago
Posts: 588
Rewards Points: 500
Send a message via AIM to Grumpy Send a message via MSN to Grumpy Send a message via Yahoo to Grumpy
Default

Roof Blowing off


I'd definetly file a complaint. IKO aren't the best shingles around but certainly not the worst.

Are you saying the seal strips were not removed? Staples suck, but allowed by code in some areas. Common tar paper? Do you mean they used no underlayment, or they used different types in different areas?

Please take pictures of the underlayment. If you have any kind of warranty at all I'd call the rooer and builder and give em a piece of mind. It sounds like something went terribly wrong with the installation. You may as well have IKO send out a rep to verify if the roof was installed properly.

If it's as bad as you make it seam, you may be better of tearing off the roof and doing it right. If it's not that bad you can get mastic in a caulk tube and put a dab under the shingles that flap in the wind. This will hold em down.

Advertisement

__________________
-Grumpy
Chicago Roofing Chicago Gutters

Sometimes the savings that comes from doing it yourself can be blown away with one mistake.

The information found in this post is not to be considered legal advice. All information should be considered relative, not specific. Never attempt any repairs you are not comfortable with. Always maintain safety! The author of this post takes no responsibility for any losses that occur. Use at your own risk.
Grumpy is offline   Reply With Quote
Old 04-25-2004, 09:46 AM   #3
Guest
Guest
 
Posts: n/a
Default

Roof Blowing off


Quote:
Originally Posted by Unregistered
our home was built new in 09/2001. Since the first winter we have been loosing shingles every time the winds go over 30mph. The shingles are IKO DHB Cambridge 25 yr. I noted that the clear plastic strip over the adhesive is still present on the ones that have blown off. The shingles were stapled on the home for some reason instead of nailed. We have even lost shingles after they were repaired by the contractor. I also noted that they did not use a common tar paper underneath the shingles. It looks like some kind of recycled paper and it is light brown in color, so you know what that is?
I have also noted that when the wind blows I can see A LOT of shingle ends coming up in the breeze. I am very concerned. Can you advise?
Thanks Don.
Don,
I built a house in the spring of 2000 and put IKO Cambridge 25 shingles on in August 2000, I had shingles blow off the roof in Feb.2001 and every Feb/March since!!
I have had a three year running battle with IKO, the shingles never sealed properly and I have had to repair my roof six times so far.
I am trying to get IKO to replace the entire roof for me, they no longer have the Cambridge 25 in their product line up, no surprise!!
I would love to hear from you on any other responses you've had on your e-mail, my address is: dlindsay@royallepage.ca
It took IKO two years to get an inspector up to look at my roof and after two minutes up top he said there was a problem with the shingles!!
That was last year and I'm still fighting with them.

Regards,

Doug
  Reply With Quote
Old 05-29-2004, 09:07 AM   #4
Member
 
Grumpy's Avatar
 
Join Date: Dec 2003
Location: Chicago
Posts: 588
Rewards Points: 500
Send a message via AIM to Grumpy Send a message via MSN to Grumpy Send a message via Yahoo to Grumpy
Default

Roof Blowing off


All 25 architectural shingles, well not all but most, were upgraded to 30-year with no change to design or manufacturing process. Cambridge 25 is now cambridge 30. The 30 became 40 and so forth.

What is your roofer doing to help you Doug?
__________________
-Grumpy
Chicago Roofing Chicago Gutters

Sometimes the savings that comes from doing it yourself can be blown away with one mistake.

The information found in this post is not to be considered legal advice. All information should be considered relative, not specific. Never attempt any repairs you are not comfortable with. Always maintain safety! The author of this post takes no responsibility for any losses that occur. Use at your own risk.
Grumpy is offline   Reply With Quote
Old 12-20-2004, 12:39 PM   #5
Newbie
 
Join Date: Dec 2004
Location: COLUMBUS, OHIO
Posts: 1
Rewards Points: 10
Default

Roof Blowing off


Don,
I hope you've resolved the problem by now, but I wanted to clear up your concern about the "clear tape strip" on the back of the shingle not being pulled off.
Well, that clear strip is there to keep the shingles from bonding together while still in the package (or bundle).
The IKO people are the ones you want to contact directly, not your roofer, as they want to resolve your concerns.
There are a number of reasons shingles blow off, high nailing or in your case staples that are "arked" (where the staple has been applied at an angle), lack of fasteners or proper fastening techniques.
Hope this helps..
Spike
spike1 is offline   Reply With Quote
Old 12-20-2004, 03:45 PM   #6
Member
 
Join Date: Nov 2004
Posts: 160
Rewards Points: 150
Default

Roof Blowing off


Quote:
Originally Posted by spike1
I wanted to clear up your concern about the "clear tape strip" on the back of the shingle not being pulled off.
Well, that clear strip is there to keep the shingles from bonding together while still in the package (or bundle).
It's still not clear to me - does the clear tape strip need to be removed upon application of the shingle or is it designed to just 'melt away' by itself?
pipeguy is offline   Reply With Quote
Old 12-22-2004, 06:02 PM   #7
Member
 
Grumpy's Avatar
 
Join Date: Dec 2003
Location: Chicago
Posts: 588
Rewards Points: 500
Send a message via AIM to Grumpy Send a message via MSN to Grumpy Send a message via Yahoo to Grumpy
Default

Roof Blowing off


Usually it is not to be removed anymore. The plastic has been engineered to disolve into the asphalt. Years past it was a requirement to remove the strips, but not any longer.
__________________
-Grumpy
Chicago Roofing Chicago Gutters

Sometimes the savings that comes from doing it yourself can be blown away with one mistake.

The information found in this post is not to be considered legal advice. All information should be considered relative, not specific. Never attempt any repairs you are not comfortable with. Always maintain safety! The author of this post takes no responsibility for any losses that occur. Use at your own risk.
Grumpy is offline   Reply With Quote
Old 01-11-2005, 11:29 AM   #8
Newbie
 
Join Date: Jan 2005
Location: Central Ontario. Canada
Posts: 8
Rewards Points: 10
Default

Roof Blowing off


A lot also depends on the time of year the shingles were installed. In warmer sunny weather the shingles will 'fuse' together more.

Advertisement

Hube is offline   Reply With Quote
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Please help with the design of this roof jaymay75 Building & Construction 1 05-06-2008 10:44 AM
leaking tar and gravel roof meleis Roofing/Siding 9 01-05-2008 11:27 PM
Flat roof - Rolled? - leaks Advice? JJ2001 Roofing/Siding 4 11-19-2006 07:17 AM
Venting a shed roof with 2/12 slope atulc Roofing/Siding 5 08-25-2006 08:28 AM
flat roof leak snikda9 Roofing/Siding 16 01-26-2006 05:25 PM




Top of Page | View New Posts