I had a new hot water base board boiler installed about 10 yrs ago and I have a problem of air build up every year. About 9 years ago I put in a new expansion tank and that did not help. I have to bleed the air out in the winter about every 3 weeks or so. Someone said it could be my water make up value. So I lowered the boiler press to 10 psig and after 3 day the press was still 10 lbs. So the value is not leaking water. The make up value rating is 12 to 15 psig but the boiler is operating at 20 lbs just under the 25 lbs for the blow off. Any suggestions


Last edited by roger kadash; 10-27-2010 at 09:37 AM.
roger kadash is offline   Reply With Quote
Old 10-27-2010, 12:12 PM   #2
Member
 
Join Date: Apr 2007
Posts: 558
Rewards Points: 500
Default

Hot Water Boiler


Can you post pictures of all the near-boiler piping? Sounds to me like the installer did not put in an air scoop or Spirovent.

Ishmael is offline   Reply With Quote
Old 10-27-2010, 12:27 PM   #3
Newbie
 
Join Date: Oct 2010
Location: Brick NJ
Posts: 2
Rewards Points: 10
Default

Hot Water Boiler


In work now ,but yea I can post pictures of the piping. However this was a replacement to the old boiler so the piping stay just about the same
roger kadash is offline   Reply With Quote
Old 10-28-2010, 10:37 PM   #4
Still going...
 
ChrisDIY's Avatar
 
Join Date: Jan 2010
Location: Indianapolis Area
Posts: 985
Rewards Points: 500
Blog Entries: 19
Default

Hot Water Boiler


I have a hot water system with a spirovent and it still gets air in it. When I lived there about three months into the winter I would get a gurgle. I was told that since my home is three stories that the water pressure needed to fill the system all the way up exceeded the city pressure so would always have some residual air in it. If the water make up valve has failed the water isn't being replenished or topped off. Just isn't backflowing?
__________________
--Chris the DIY Guy

Master Bath, still going...

Last edited by ChrisDIY; 10-28-2010 at 10:40 PM.
ChrisDIY is offline   Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Adding Hot water Heater To Boiler kchamb1206 Plumbing 7 09-05-2010 09:08 PM
boiler and hot water venting AdamBNYC Plumbing 3 08-26-2010 05:09 PM
water borehole question joeuser General DIY Discussions 2 04-18-2010 10:33 PM
Boiler size Bonnie Youngs HVAC 29 07-10-2009 07:58 PM
Testing 12 year old hot water expansion tank? DJfixer Plumbing 2 01-01-2009 08:09 AM




Top of Page | View New Posts

Copyright © 2003-2014 Escalate Media. All Rights Reserved.