Old 12-15-2008, 10:31 PM   #1
Newbie
 
Join Date: Sep 2008
Posts: 18
Rewards Points: 10
Default

Hammer time....


Not sure if this is plumbing or landscaping...I have a sprinkler system that starts with 1/2 inch copper pipe at the house and turns into 3/4 pvc with about 10 sprinklers on it...When it shuts off there is a loud bang that can be heard through out the house...Anyone else run into this??? Thnx, Jim..

Advertisement

GE JIM is offline   Reply With Quote
Old 12-15-2008, 11:46 PM   #2
Registered User
 
Termite's Avatar
 
Join Date: Apr 2008
Posts: 6,520
Rewards Points: 2,000
Default

Hammer time....


Yup, that's water hammer. It is caused by fast-acting valves like your electronic controls on the sprinkler, and those on washing machines.

Your best bet would be to look at hammer arrestors. Depending on the configuration, they make ones that you can solder to the 1/2" copper as close to the valve as possible. Sioux Chief is a popular manufacturer of them, and you can get them at box stores or plumbing supply houses.

Advertisement

Termite is offline   Reply With Quote
Old 12-16-2008, 05:46 PM   #3
Newbie
 
Join Date: Sep 2008
Posts: 18
Rewards Points: 10
Default

Hammer time....


Thanks Termite for getting back to me...I"ll look for those and see if it helps...Jim..
GE JIM is offline   Reply With Quote
Old 12-16-2008, 07:51 PM   #4
Registered User
 
Termite's Avatar
 
Join Date: Apr 2008
Posts: 6,520
Rewards Points: 2,000
Default

Hammer time....


Here's what they look like...
Termite is offline   Reply With Quote
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Subpanels & cutler hammer arc fault breakers MoreCowbell Electrical 13 04-04-2008 11:19 PM
First time vinyl siding newbie plus windows justdon Remodeling 9 02-06-2008 07:39 PM
Best cordless hammer drill for occasional use jaym3 Tools 6 11-11-2007 08:26 PM
hammer tacker/stapler Clutchcargo Building & Construction 2 09-20-2007 09:28 AM
water hammer question seanstoner Plumbing 7 04-10-2006 05:28 PM




Top of Page | View New Posts