Does my rough plumbing look ok?


Hello all.

Before I put on the glue, I was wondering if I could get some comments on my current drain/vent set up for my 1/2 bath in my basement.

My attached pictures have my future layout with the to be drain/vent.

My rough in plumbing has the 4" toilet drain and a 3" sink drain. In the floor joices above there was a 2" vent stack that was capped and ready for me to tie into.

I ran the 2" vent down and then horizontally 2 feet until it could hook up to the vertical part of the vent where I have a 1 1/2 inch sink drain tieing in with a sanitary tee where I will eventually put a 90 degree and link it into my sink once I determine where officially go.

Future water supply lines will come down from my ceiling once I tie into the water lines.

Questions, does this look acceptable? I am a little nervouse because all the reseach I have done usually always shows a seperate vent stack for the toilet which I dont have one. So will it still work??

My toilet flange is just on the pipe, I need to cut the pipe once I get closer to setting the tile so that is why it is that high.

Also, does anyone know a good way to finish off a back water check valve? I was hoping to just be able to buy a floor drain cover and replace the plastic lid.

Any advice is greatly appreciated.
Attached Thumbnails
Does my rough plumbing look ok?-bathroom_520x380.jpg   Does my rough plumbing look ok?-bathroom2_520x380.jpg  

KYoung2000 is offline   Reply With Quote
Old 02-18-2012, 10:45 AM   #2
Member
 
Join Date: Oct 2009
Location: Minneapolis, MN
Posts: 492
Default

Does my rough plumbing look ok?


Not sure if I understand the 2" horizontal PVC pipe supported by the 2x4 piece where the vanity is going. Is this the drain back to the wall or the vent back to the wall? I know the vent can not go horizontal until it is above the flood plain (vanity top) of the device it is venting.

You may have two pipes running horizontal to the drain by the wall: the drain at trap height and the vent 2-3 feet higher.

B

Beepster is offline   Reply With Quote
The Following User Says Thank You to Beepster For This Useful Post:
KYoung2000 (02-18-2012)
Old 02-18-2012, 11:04 AM   #3
Newbie
 
Join Date: Feb 2012
Posts: 5
Default

Does my rough plumbing look ok?


the 2" that has the 2 x 4 supporting it will be the drain back to the vent. I just havent cut it to proper length yet and put on the 90 elbow.

I have the run sloping about 1 inch since the run from where I am anticipating the vanity to go is about 4 feet.
KYoung2000 is offline   Reply With Quote
Old 02-18-2012, 12:12 PM   #4
Member
 
Join Date: Oct 2009
Location: Minneapolis, MN
Posts: 492
Default

Does my rough plumbing look ok?


I am not sure if a vanity drain can run that far before being vented. You could ask the plumbing inspector at your city hall (is this going to be inspected?) or you could just run a vent up and over as I previously mentioned.

B
Beepster is offline   Reply With Quote
Old 02-18-2012, 01:55 PM   #5
moderator
 
TheEplumber's Avatar
 
Join Date: Jul 2010
Location: Idaho
Posts: 6,613
Default

Does my rough plumbing look ok?


Here's a couple things I'd do-
Install a 3" cleanout on the vent, then reduce it to 2".
Pipe the lav trap arm with 1.5"- max length= 42" per UPC (what code is used in your area)
check at http://www.siouxchief.com/ for something to cover the BW valve.
TheEplumber is online now   Reply With Quote
The Following User Says Thank You to TheEplumber For This Useful Post:
ben's plumbing (02-18-2012)
Old 02-18-2012, 05:29 PM   #6
Master Plumber
 
Javiles's Avatar
 
Join Date: Dec 2011
Location: Miami Florida
Posts: 1,304
Default

Does my rough plumbing look ok?


What aim quoting is under the IPC
1 hard to tell is that a wye at the stack and sink waste arm.? If it is must be a sanitary tee not a wye.
2 waste arm to sink 5 feet from stack in 1 pipe 2” 8 feet.
3 how are you picking up the toilet? Within 5 feet of the vent
4 clean out at the base of the stack. As someone mentioned.
__________________


Experience is Knowing what to do next, Skill is knowing how to do it

http://www.americandrain.net
Javiles is offline   Reply With Quote
Old 02-18-2012, 05:56 PM   #7
retired elect/hvac/plumb
 
plummen's Avatar
 
Join Date: Jan 2010
Location: south east of omaha/The island of misfit contractors
Posts: 2,889
Default

Does my rough plumbing look ok?


I wouldnt worry about running that waste arm for vanity till the walls are framed up.
Is anything tied into that 3" line above it like a toilet?
__________________
"facts" have no relevance to this discusion
Posting from a concrete bunker under a non descript barn
plummen is offline   Reply With Quote
Old 02-18-2012, 06:10 PM   #8
Newbie
 
Join Date: Feb 2012
Posts: 5
Default

Does my rough plumbing look ok?


Quote:
Originally Posted by Javiles View Post
What aim quoting is under the IPC
1 hard to tell is that a wye at the stack and sink waste arm.? If it is must be a sanitary tee not a wye.
2 waste arm to sink 5 feet from stack in 1 pipe 2 8 feet.
3 how are you picking up the toilet? Within 5 feet of the vent
4 clean out at the base of the stack. As someone mentioned.

Thanks for the follow up....

1) Yes it is a sanitary tee. Made sure of it when I bought it.
2) thanks, my 1 1/2 waste arm should not be more than 4 feet, so I should be good.
3. The toilet is just roughed in where it is in the picture. I am not sure there is a vent for the toilet. I just have the 4 inch pipe sticking out of the concrete in which I just placed a flange for the picture. that is one of my main concerns. I am assuming that the toilet and 3" drain both route back to the backwater valve and then to my house main stack drain that sits just in back of this picture about 4 feet.
4) clean out bought this afternoon
KYoung2000 is offline   Reply With Quote
Old 02-18-2012, 06:13 PM   #9
Newbie
 
Join Date: Feb 2012
Posts: 5
Default

Does my rough plumbing look ok?


Quote:
Originally Posted by plummen View Post
I wouldnt worry about running that waste arm for vanity till the walls are framed up.
Is anything tied into that 3" line above it like a toilet?

Correct, I wont be running the waste arm until the walls go up, I just wanted conceptually to show what will be going on.

actually the line going up is a 2" vent stack, its a 3" into cement. I added a reducer just before the floor and below the sanitary tee. nothing is about that line it just links into a pre-installed vent stack that was in place within the floor joist.
KYoung2000 is offline   Reply With Quote
Old 02-18-2012, 06:13 PM   #10
retired elect/hvac/plumb
 
plummen's Avatar
 
Join Date: Jan 2010
Location: south east of omaha/The island of misfit contractors
Posts: 2,889
Default

Does my rough plumbing look ok?


Toilet vent should already be tied in under the floor during rough in of house
__________________
"facts" have no relevance to this discusion
Posting from a concrete bunker under a non descript barn
plummen is offline   Reply With Quote
The Following User Says Thank You to plummen For This Useful Post:
KYoung2000 (02-18-2012)
Old 02-18-2012, 06:19 PM   #11
Member
 
Join Date: Oct 2011
Location: pa
Posts: 4,275
Default

Does my rough plumbing look ok?


you have the right idea and your install should be fine... vent for commode is already tied in under floor I would as mentioned install 3" clean out then reduce for vent... and vanity drain...
ben's plumbing is offline   Reply With Quote
The Following User Says Thank You to ben's plumbing For This Useful Post:
KYoung2000 (02-18-2012)
Old 02-18-2012, 06:54 PM   #12
Newbie
 
Join Date: Feb 2012
Posts: 5
Default

Does my rough plumbing look ok?


Thanks for all of the advice!! Very much appreciated!!

KYoung2000 is offline   Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Installing Plumbing in a basement with No rough ins simpsjm1 Plumbing 8 12-20-2011 10:40 PM
what to do for plumbing rough inspection? red86yota Plumbing 5 09-12-2010 04:39 PM
Basement bathroom rough in plumbing ferris13 Plumbing 5 09-28-2009 10:06 AM
Rough underground plumbing for basement bathroom JTK Plumbing 1 07-23-2008 08:30 AM
rough in plumbing psiter Plumbing 5 08-23-2006 05:44 PM




Top of Page | View New Posts

Copyright © 2003-2014 Escalate Media. All Rights Reserved.