DIY Chatroom -  DIY Home Improvement Forum
    DIY Forum     DIY Blogs     Photos     Woodworking     Advertise     Contact Us  

CLICK HERE AND JOIN OUR COMMUNITY TODAY...IT'S FREE!
Go Back   DIY Chatroom - DIY Home Improvement Forum > Home Improvement > Plumbing

Reply
 
Thread Tools Search this Thread Display Modes
Old 10-25-2012, 01:56 PM   #1
Member
 
Join Date: Sep 2011
Location: Chicago, IL
Posts: 40
Default

"Chicago-Loop" For Shower & Laundry Room Vent


Can I use the Chicago Loop, as shown in the photo, to vent a shower & Laundry room drain?

Im a novice when it comes to plumbing and am trying to learn here. While I don't think its ideal - I want to use this as I have a vent pipe that exits the roof behind a short knee wall. There is really no way for me to traditionally tap into it as the shower/laundry room are about 10 feet away from it and a bathroom entry door also proposes an additional obstacle.
Attached Images
 


Last edited by spaceboy; 10-25-2012 at 02:36 PM.
spaceboy is offline   Reply With Quote
Join DIYChatroom.com

Join the #1 DIY Forum Today - It's Totally Free!

DIYChatroom.com - Are you about to start a new home improvement task and need some help? Do you need advise on what products to buy? Or maybe you can give others some advice? No matter where you fit in you'll find that DIY Chatroom is a great community to join. Best of all it's totally free.

Join DIYChatroom.com - Click Here
JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. DIYChatroom.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any home improvement task!
Old 10-25-2012, 02:51 PM   #2
Member
 
Join Date: Oct 2009
Location: Minneapolis, MN
Posts: 395
Default

"Chicago-Loop" For Shower & Laundry Room Vent


Maybe take a picture of your situation.

I think to what you are referring is only used on kitchen islands and similar areas where there is absolutely no other way to vertically vent.

I will let pros pipe in on this.

B

Beepster is offline   Reply With Quote
Old 10-25-2012, 03:03 PM   #3
Member
 
Join Date: Sep 2011
Location: Chicago, IL
Posts: 40
Default

"Chicago-Loop" For Shower & Laundry Room Vent


Quote:
Originally Posted by Beepster View Post
Maybe take a picture of your situation.

I think to what you are referring is only used on kitchen islands and similar areas where there is absolutely no other way to vertically vent.

I will let pros pipe in on this.

B
Thanks... Thats exactly what i have been thinking about - I have not seen this used/referenced for anything other than a kitchen island installation.

I did a quick "rough" floorplan layout of what the attic will look like - maybe this helps.... the black dot marks the spot of the current vent location.

what about going up above the door frame then dropping to the horizontal vent run for the sink?- would that work?

I have read both yes and no to that - the yes version says as long as the vent is 6" above the highest fixture served by the runs - it will be ok.
Attached Images
File Type: bmp Vent PipeII.bmp (11.6 KB, 110 views)

Last edited by spaceboy; 10-25-2012 at 03:44 PM.
spaceboy is offline   Reply With Quote
Old 10-26-2012, 08:41 AM   #4
Master Plumber
 
Javiles's Avatar
 
Join Date: Dec 2011
Location: Miami Florida
Posts: 924
Default

"Chicago-Loop" For Shower & Laundry Room Vent


set up worked for many years and was code approved under the old code. no longer approved under the IPC, if you go with that set up youll need clean outs at the end of each loop. also it was meant to be used in lines 3 inch and up.
__________________


Experience is Knowing what to do next, Skill is knowing how to do it


To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.
Javiles is offline   Reply With Quote
Reply


-->
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Laundry Room Divider - Help! Soxckersfc2002 Carpentry 1 05-07-2011 02:50 PM
Water Tight Laundry Room (prevent water from spilling over into other rooms) asummit Remodeling 6 03-29-2011 06:17 AM
Attic Ventilation Question handy man88 Roofing 10 02-12-2010 11:50 PM
Supply and Return from Laundry Room bjstewa HVAC 7 03-03-2007 12:39 AM
Replacing a laundry room roof. Tomcat1066 Building & Construction 5 11-11-2006 04:08 PM


Top of Page | View New Posts


All times are GMT -4. The time now is 03:58 AM.


© 2003 - 2010 The Building Network LLC