Hole above Heating Unit


We purchased a home not lone ago and the gas heating unit is in a semi type hall closet. The closet is about 2 1/2 feet wide and 4 1/2 feet long. Looking up, I see silver ductwork running in several directions and then I see the roof of the house. Is this normal? This "closet" has no ceiling, just the roof ! Advice needed.

Advertisement

lckennedy303 is offline   Reply With Quote
Old 06-10-2009, 12:14 PM   #2
Newbie
 
Join Date: Dec 2008
Posts: 2
Rewards Points: 10
Default

Hole above Heating Unit


It could that way to allow fresh combustion air for the furnace.

Advertisement

corriewolfe is offline   Reply With Quote
Old 06-10-2009, 01:31 PM   #3
Household Handyman
 
Join Date: Feb 2009
Location: Albany, Ga.
Posts: 2,301
Rewards Points: 1,054
Default

Hole above Heating Unit


I can't give you the exact correct answer on this, but these units are very common in my area and they are all that way, with the opening at the top. Maybe it does have something to do with ventilation for combustion IF you have gas heat. However, I do know this, my Mom's house had an infiltration of honey bees a few years ago in the attic. These bees made their way into this HVAC closet and through the cracks of the door to the closet into the house. Quite a scare for her! After we got rid of the bee problem I placed screen wire over the opening so there could be ventilation but keep the buggies out. My two cents worth, David.
Thurman is offline   Reply With Quote
Old 06-10-2009, 01:59 PM   #4
Newbie
 
Join Date: Jun 2009
Posts: 2
Rewards Points: 10
Default

Hole above Heating Unit


Good idea. We do have a lot of bats in this area.
lckennedy303 is offline   Reply With Quote
Old 06-11-2009, 08:54 AM   #5
Registered User
 
Termite's Avatar
 
Join Date: Apr 2008
Posts: 6,520
Rewards Points: 2,000
Default

Hole above Heating Unit


I'd almost guarantee that they're combustion air vents, and they are needed/required. The screen wire idea is a good one! If the furnace is in a hallway and not in a closet that opens via a bedroom, another option is to install a fully louvered door.
Termite is offline   Reply With Quote
Reply

Tags
hole in ceiling , no insulation


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Loud intermittent Metallic sound from Heating Unit uy7473 HVAC 2 01-21-2009 05:15 PM
Most efficient heating unit farooq Plumbing 1 08-02-2008 05:19 PM
Heating Unit farooq Plumbing 2 07-18-2008 06:23 PM
AC or heating unit just will not come on lilda12 HVAC 4 06-16-2008 07:44 PM
Trane XE80 Heating Question, Please help!!! Stephen1977 HVAC 3 01-30-2007 07:34 PM




Top of Page | View New Posts