Soffit Vents


In the process of updating my attic ventilation. Current question pertains to my soffit intake vents. I plan to balance intake/exhuast at 1NFA/150ft2.

The current soffit is aluminum and while it appears to be perforated for airflow, I checked underneath and sure enough, there is a solid board underneath. Based on how everything else in this house has gone (built in '56) I'm feel fairly confident that the soffit is solid wood the length of the house. My dad feels there should be holes cut in the wood for ventilation prior to the aluminum soffit being installed. I agree that it "should" be that way but really don't think it is based on the current ventilation set up (1 12" turbine for 1500 ft2 of attic space).

This is what I want to do.... Determine how many 16" x 8" soffit vents I need based on my exhaust system and NFA calculations. (Going to be around 11ish). Then go around the perimeter of the house and drill/cut through the aluminum/wood soffits and install the vents evenly spaced.

Anyone see any issues with my plan?

Advertisement

Atskodinski is offline   Reply With Quote
Old 03-05-2011, 07:18 AM   #2
Member
 
Join Date: Jan 2009
Location: WV
Posts: 3,028
Rewards Points: 2,236
Default

Soffit Vents


Do you have any roof vents? A ridge vent? The air you want to let in has to get out somewhere.

Advertisement

md2lgyk is offline   Reply With Quote
Old 03-05-2011, 07:28 AM   #3
Experienced
 
Jackofall1's Avatar
 
Join Date: Dec 2010
Location: Southern Michigan
Posts: 2,822
Rewards Points: 2,000
Default

Soffit Vents


I would be looking at equivalent mushroom caps or ridge vent (but that would mean more roofing work) as opposed to a turbine vent, to attempt to get more uniform flow through the attic.

Mark

Edit - heres a great site if you are interested

http://www.buildingscience.com/docum...ic-ventilation
__________________
When its all said and done there is usually more said than done

Last edited by Jackofall1; 03-05-2011 at 07:31 AM.
Jackofall1 is offline   Reply With Quote
Old 03-05-2011, 10:55 AM   #4
Member
 
Join Date: Mar 2007
Location: Long Island, NY
Posts: 9,519
Rewards Points: 2,000
Default

Soffit Vents


Quote:
Originally Posted by Atskodinski View Post
In the process of updating my attic ventilation. Current question pertains to my soffit intake vents. I plan to balance intake/exhuast at 1NFA/150ft2.

The current soffit is aluminum and while it appears to be perforated for airflow, I checked underneath and sure enough, there is a solid board underneath. Based on how everything else in this house has gone (built in '56) I'm feel fairly confident that the soffit is solid wood the length of the house. My dad feels there should be holes cut in the wood for ventilation prior to the aluminum soffit being installed. I agree that it "should" be that way but really don't think it is based on the current ventilation set up (1 12" turbine for 1500 ft2 of attic space).

This is what I want to do.... Determine how many 16" x 8" soffit vents I need based on my exhaust system and NFA calculations. (Going to be around 11ish). Then go around the perimeter of the house and drill/cut through the aluminum/wood soffits and install the vents evenly spaced.

Anyone see any issues with my plan?
Sounds like a plan. The house probably had some venting in the soffit area originally, but the siding guys just ignored their locations and were too lazy to take the time to cut through the plywood for the new vents that lined up with their work. I just went to a customers house to check for insulation in the attic. Saw somebody used a drill to "vent" the soffits when the vinyl went in to cap the overhangs. I'm sure the 5, 1/2" holes went a long way to solve the venting issue.
Ron
Ron6519 is offline   Reply With Quote
Old 03-05-2011, 11:19 AM   #5
Member
 
Join Date: Nov 2010
Posts: 84
Rewards Points: 75
Default

Soffit Vents


Quote:
Originally Posted by md2lgyk
Do you have any roof vents? A ridge vent? The air you want to let in has to get out somewhere.
I'm working with a roofer to put in an appropriate ridge vent. Like I said, I do plan to balance my system. I'm just asking here about my plans for the soffit vents since that is the part I plan to tackle myself.

The other thing I should point out is the existing metal soffit's perforated sections have either been painted over to cover up the holes or they are more decorative in nature. So even if there are holes in the plains above, can't imagine much air is getting through. I currently have 1 turbine that never spins, which I attribute to no intake air (bearings on it have been checked).

I assume to issues cutting/drilling through the metal soffit?
Atskodinski is offline   Reply With Quote
Old 03-05-2011, 01:15 PM   #6
Member
 
Join Date: Nov 2010
Posts: 84
Rewards Points: 75
Default

Soffit Vents


Quote:
Originally Posted by Ron6519 View Post
Sounds like a plan. The house probably had some venting in the soffit area originally, but the siding guys just ignored their locations and were too lazy to take the time to cut through the plywood for the new vents that lined up with their work. I just went to a customers house to check for insulation in the attic. Saw somebody used a drill to "vent" the soffits when the vinyl went in to cap the overhangs. I'm sure the 5, 1/2" holes went a long way to solve the venting issue.
Ron
Hey Ron, thatnks for the input.

Did some additional investigating and sure enough, I did find a vent screwed into the original wood soffit. Of course, like you said, there is a solid piece instead of a perforated piece over that vent. Obviously not much care went into lining everyhing up or cutting additional holes in the wood soffit. Also can confirm the metal soffit has been painted over which further reduces the openings of the perforforated sections. It seems to me that whatever ventilation currently exists is minimal at best and unless I want to rip down the exisiting soffit to cut new holes, clean the paint clogging the perforated section, I think my plan will still work. Obviously just need to avoid cutting into an existing vent.
Atskodinski is offline   Reply With Quote
Old 03-05-2011, 01:19 PM   #7
Member
 
Join Date: Jun 2008
Posts: 855
Rewards Points: 526
Default

Soffit Vents


only way I see to get this 'right' is to take off existing metal soffit and then remove all of the plywood, cutting it if necessary. Making sure your rafter bays are open to the peak,,,or sidewalls arent solid to roof. Put insulation baffles as necessary. Put your soffit material back on if it indeed vents,,,if not install 'new' vented soffit.

Advertisement

4just1don is offline   Reply With Quote
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Vinyl Perf Soffit over Wood - No Vents nickelshine Roofing/Siding 18 05-29-2012 10:12 AM
Soffit Vents for Wooden Soffit? rollenrock33 Roofing/Siding 2 12-27-2010 07:16 PM
No soffit vents needed? MikeNY Roofing/Siding 4 08-24-2010 05:30 PM
Installing Soffit vents w/finished attic Nathan0115 Roofing/Siding 6 06-04-2010 10:05 PM
Soffit vents on older houses with "curved" ceilings Labman101 Roofing/Siding 2 02-07-2010 11:33 PM




Top of Page | View New Posts