Quote:
Originally Posted by Saturday Cowboy
must run from main panel to ufer!
|
This is a detached structure with a 60A feeder. See original post.
Quote:
Originally Posted by Saturday Cowboy
Size is based on feeder size.
|
#6 ungrounded conductors. See original post.
Quote:
Originally Posted by Saturday Cowboy
You most likely have #2al or #4cu for your feeders. (guessing main panel is 100A)
|
Again, see original post.
Quote:
Originally Posted by Saturday Cowboy
In which case #6al or #8cu, should be larger enough for your UFER GEC.
|
This is correct, and is also the minimum size GEC.