wwkorn 02-04-2013 07:54 PM

Smurf tubing
 
i have a empty 3/4 inch blue smurf tube that i want to use to go to a J box and supply a instant hot water heater which requires 8ga and a AC unit that requires 10ga both 230volt, will all the wires fit in the 3/4 inch tube ?? and is it ok to run the 3/4 tube to a junction box and then go to the 2 different units ?

TarheelTerp 02-04-2013 08:56 PM

Quote:

Originally Posted by wwkorn (Post 1109695)
i have a empty 1 inch blue smurf tube that i want to use to go to a J box and supply a instant hot water heater which requires 8ga and a AC unit that requires 10ga both 230volt, will all the wires fit in the 1 inch tube ??

2 #8's and 2#10's (+ ground) will fit in 1" ENT with room to spare.

wwkorn 02-04-2013 08:58 PM

change in size
 
i just revised my post , i have 3/4 not 1 inch

curiousB 02-05-2013 05:30 AM

Isn't smurf tube for comms circuits cat5 and RG6?

sgip2000 02-05-2013 11:26 AM

Quote:

Originally Posted by curiousB (Post 1109915)
Isn't smurf tube for comms circuits cat5 and RG6?

In some areas, it is allowed for line voltage.