Smurf (flex ent) use Code clarification


HI;

In the garage, the ceiling is unfinished, just open joists. It is not going to be finished. This is a residential garage, for parking cars, no work shop or anything special in this garage; 2 cars, some storage, and a 240v compressor.

I am wondering if it is considered acceptable to run "smurf" in the ceiling, even though it is exposed, if I keep it between the joists and drill holes where it crosses the joists?

Also, when I come down to just below a joist to a junction box, can the smurf dip just below the joist at that point to enter the jbox? or does it have to stay between the joists entirely.

I'd use EMT on the walls, for the drops down to the panel and to the switches / outlets. It's just in the ceiling and in the attic that I was thinking of running EMT. I was just looking to save a little time over using EMT for everything.

One other quick question on smurf, can it be used in a crawl space below the joists? What if I keep it at the running board?

Thanks
Jamie

__________________
Jamie Dolan - Neenah, WI
Jamie Dolan Paw Dogs
Need Help Uploading Photos? Click here.
jamiedolan is offline   Reply With Quote
Old 02-02-2009, 05:26 PM   #2
Electrician
 
Join Date: Aug 2007
Location: Connecticut, Litchfield
Posts: 2,015
Rewards Points: 1,000
Default

Smurf (flex ent) use Code clarification


Quote:
Originally Posted by jamiedolan View Post
HI;

In the garage, the ceiling is unfinished, just open joists. It is not going to be finished. This is a residential garage, for parking cars, no work shop or anything special in this garage; 2 cars, some storage, and a 240v compressor.

I am wondering if it is considered acceptable to run "smurf" in the ceiling, even though it is exposed, if I keep it between the joists and drill holes where it crosses the joists?

Also, when I come down to just below a joist to a junction box, can the smurf dip just below the joist at that point to enter the jbox? or does it have to stay between the joists entirely.

I'd use EMT on the walls, for the drops down to the panel and to the switches / outlets. It's just in the ceiling and in the attic that I was thinking of running EMT. I was just looking to save a little time over using EMT for everything.

One other quick question on smurf, can it be used in a crawl space below the joists? What if I keep it at the running board?

Thanks
Jamie
In my area I would just use NM... As long as the garage was attached anyways.

chris75 is offline   Reply With Quote
Old 02-02-2009, 05:54 PM   #3
Member
 
Join Date: Jul 2008
Location: Iowa
Posts: 1,543
Rewards Points: 1,000
Default

Smurf (flex ent) use Code clarification


Quote:
Originally Posted by chris75 View Post
In my area I would just use NM... As long as the garage was attached anyways.

If it was detached it would need a 15 min finish rating, right?
rgsgww is offline   Reply With Quote
Old 02-02-2009, 05:55 PM   #4
Electrician
 
Join Date: Aug 2007
Location: Connecticut, Litchfield
Posts: 2,015
Rewards Points: 1,000
Default

Smurf (flex ent) use Code clarification


Quote:
Originally Posted by rgsgww View Post
If it was detached it would need a 15 min finish rating, right?
Yeah, that pesky code issue. I never see anyone enforce it though.
chris75 is offline   Reply With Quote
Old 02-02-2009, 06:16 PM   #5
DIY'er
 
jamiedolan's Avatar
 
Join Date: Sep 2008
Location: Neenah, Wisconsin, USA
Posts: 2,032
Rewards Points: 1,000
Blog Entries: 2
Default

Smurf (flex ent) use Code clarification


Quote:
Originally Posted by rgsgww View Post
If it was detached it would need a 15 min finish rating, right?
Stupid me. Forgot to say it is detached.
Jamie
__________________
Jamie Dolan - Neenah, WI
Jamie Dolan Paw Dogs
Need Help Uploading Photos? Click here.
jamiedolan is offline   Reply With Quote
Old 02-03-2009, 12:18 PM   #6
Member
 
Join Date: Jun 2007
Posts: 3,508
Rewards Points: 2,004
Default

Smurf (flex ent) use Code clarification


Jamie, Now that you are getting pipe bending experience why not use pipe? Looks better than smurf or NM. I don't see much added time. Pick a method that serves you best and stick with it.
J. V. is offline   Reply With Quote
Old 02-03-2009, 01:25 PM   #7
Member
 
Join Date: Jul 2008
Location: Iowa
Posts: 1,543
Rewards Points: 1,000
Default

Smurf (flex ent) use Code clarification


Why not? Conduit looks good
rgsgww is offline   Reply With Quote
Old 02-04-2009, 12:30 AM   #8
DIY'er
 
jamiedolan's Avatar
 
Join Date: Sep 2008
Location: Neenah, Wisconsin, USA
Posts: 2,032
Rewards Points: 1,000
Blog Entries: 2
Default

Smurf (flex ent) use Code clarification


Your right, EMT does look nice, I like it alot. My dad had asked me about using some more smurf to save time, and I felt compelled to at least ask you guys about it.

After my dad spent about 4 hours trying to fish a wire today, I showed him how to save some time, it involved a sawzall

I am amazed at how fast my dad can plaster, Just an hour or two after my demo work, aside from the paint, you could barely tell anything happened to that wall, tomorrow it will be painted and will look like it always did.

Jamie

__________________
Jamie Dolan - Neenah, WI
Jamie Dolan Paw Dogs
Need Help Uploading Photos? Click here.
jamiedolan is offline   Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
code details for boxes kama Electrical 6 01-30-2009 10:25 AM
Code Clarification GoyimPersuasion Electrical 24 01-28-2009 03:44 PM
Distance between Heater & Combustibles DIY_JC Building & Construction 7 01-20-2009 07:52 AM
Another Bryant 383KVA with code 31 problems rpgIVguru HVAC 1 02-05-2007 01:47 PM
1950's Roof Framing Strength KempLN Building & Construction 21 06-17-2006 10:06 AM




Top of Page | View New Posts

Copyright © 2003-2014 Escalate Media. All Rights Reserved.