Outdoor outlet near hose bib
I want to add an outdoor hose bib to my detached garage. The "prime" location is near an exterior outlet. What does code say about separation distance between the two?
|
Nothing at all. There's no requirement other than to GFCI the receptacle. You could crowd the two together and be completely legal.
That being said, I'd keep it a foot or two away if you can, just to minimize the potential for problems and non-code-based subjective scrutiny from pre-purchase inspectors if you ever sell the place. |
Thanks for the reply. The receptacle is already on a GFCI circuit. I'll make sure I keep a reasonable distance between the two and I won't put the "spicket" directly above the receptacle.
|