OK to use schedule 40 & 80 conduit?


I am using 1 1/4 schedule 80 conduit to go across my driveway from my shop to garage and at the supply house they said to use the schedule 40 90's. They said nobody uses the schedule 80 90's plus they don't stock any. Where the 90's are is not going to be driven over. Is it acceptable?

Advertisement

Plumbvoltage is offline   Reply With Quote
Old 05-19-2009, 01:44 PM   #2
Member
 
Join Date: Oct 2007
Posts: 2,294
Rewards Points: 1,000
Default

OK to use schedule 40 & 80 conduit?


We use sched 40 exclusivly. There is no way that driving over buried conduit could come close to harming it. Sched 80 is overkill.

We also never use 1 1/4.

1 1/2 or 2" is about the same money and WAY easier to pull thru.

Advertisement

220/221 is offline   Reply With Quote
Old 05-19-2009, 03:27 PM   #3
Licensed Electrical Cont.
 
Speedy Petey's Avatar
 
Join Date: Feb 2004
Location: NY State
Posts: 6,905
Rewards Points: 2,162
Default

OK to use schedule 40 & 80 conduit?


Anywhere underground sch40 is fine. Exposed above ground and subject to damage you should use sch80.
__________________
Sometimes I feel like if I answer any more questions it is like someone trying to climb over a fence to jump off a bridge and me giving them a boost.
Answers based on the 2008 & 2011 NEC.
Speedy Petey is offline   Reply With Quote
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
ground wire in rigid conduit measure thrice Electrical 3 02-03-2009 06:25 AM
#3 AWG Copper SER / PVC Conduit Question djejay75 Electrical 4 12-12-2008 12:40 AM
Conduit for #6 wire joey b Electrical 13 11-22-2008 01:13 PM
Conduit Fill & Ampacity capndave Electrical 37 03-26-2008 03:16 PM




Top of Page | View New Posts