Meter Load Center Combo
Hello,
Im wondering if you could use a Meter Load Center Combo like the Murray JA110AS, as a subpanel safely? I would be running power to a shed with a light circuit and couple of device circuits. If it could be used, do I have to have a meter installed, or can the socket be plugged? Dont want to buy a meter if I dont have to. Reason I ask is it 100AMP,has 10 breaker spaces for 20 circuits, and local HD has them clearanced for $11.00. Thanks Mike |
|
|
|
|
|
#2 |
|
Member
Join Date: Sep 2008
Location: Oregon
Posts: 1,497
|
Meter Load Center Combo
I was going to say I wouldn't do that, then I saw the $11 price...
Hummmm??? |
|
|
|
|
|
#3 | |
|
Floor Sweeper
Join Date: Nov 2007
Location: Central MN
Posts: 347
|
Meter Load Center ComboQuote:
Problem is almost all of these are labeled, "suitable only for use as service equipment," with no way to insulate the neutral bus from the cabinet. |
|
|
|
|
|
|
#4 |
|
yeah, right
Join Date: Jan 2009
Location: California
Posts: 142
|
Meter Load Center Combo
You mean like this?
__________________
Honey, does this tool belt make me look FAT? |
|
|
|
|
|
#5 |
|
Floor Sweeper
Join Date: Nov 2007
Location: Central MN
Posts: 347
|
Meter Load Center Combo |
|
|
|
![]() |
| Thread Tools | Search this Thread |
| Display Modes | |
|
|
Similar Threads
|
||||
| Thread | Thread Starter | Forum | Replies | Last Post |
| Flush mount an outdoor load center? | wmldwilly | Electrical | 1 | 04-29-2009 08:17 PM |
| Load center vs. bottom fed Panel Board. Ugh. | wmldwilly | Electrical | 8 | 04-23-2009 08:48 PM |
| Load Center Replacement - with or w/o main breaker? | shepiii | Electrical | 3 | 01-30-2009 12:04 PM |
| Termite repair to load center wall - precautions | shepiii | Electrical | 3 | 01-21-2009 05:14 PM |
| Load Center | dwayne | Electrical | 4 | 07-09-2006 02:02 PM |