GFCI nuisance tripping


My wife has been complaining that the receptacles in the basement aren't working. I added some last summer and put them all on a single GFCI. They would work fine, then she'd go down and plug something in. No power.

She would reset the GFCI, everything would work perfectly then a couple of days later.... the same thing.

I pulled the cover and the connections were right, tight, no problem. Still, the problem persisted, apparently under no load at all. We would turn everything off, and it wouldn't come on, but the GFCI would be in a tripped condition before we turned on anything.

I was ready to replace it, but was down in the basement with our toddler yesterday, and while I was getting clothes out of the dryer I heard her moving a chair. She climbed up, pushed the 'test' button and giggled.

"Happy, Happy, Happy!" she exclaimed.

Note to self: install future GFCI out of areas "easily accessible' to toddlers. I might want to suggest this as a code change for the next NEC cycle.

Bigplanz is offline   Reply With Quote
Old 04-30-2009, 11:24 AM   #2
Member
 
Join Date: Jul 2008
Location: Iowa
Posts: 1,543
Default

GFCI nuisance tripping


Maybe press two buttons simultaneously to test a gfci?

rgsgww is offline   Reply With Quote
Old 04-30-2009, 11:43 AM   #3
Tool Geek
 
PaliBob's Avatar
 
Join Date: Jun 2008
Location: Pacific Palisades CA
Posts: 2,502
Default

GFCI nuisance tripping


The new TR GFCI's Missed that when they came up with the name
Tamper Resistant
.
__________________
Disclaimer
& Stay Safe
.....Bob Lavery
PaliBob is offline   Reply With Quote
Old 04-30-2009, 11:58 AM   #4
Member
 
Bigplanz's Avatar
 
Join Date: Apr 2009
Location: Louisville KY
Posts: 516
Default

GFCI nuisance tripping


Quote:
Originally Posted by PaliBob View Post
The new TR GFCI's Missed that when they came up with the name
Tamper Resistant
.
The tamper resistance they are referring to is a shutter system that won't allow a child (or anyone) to put a paper clip/screwdriver/whatever in the hot slot of a receptacle.
Bigplanz is offline   Reply With Quote
Old 04-30-2009, 11:59 AM   #5
Member
 
Join Date: May 2008
Location: Apple Valley, MN, USA
Posts: 999
Send a message via AIM to theatretch85
Default

GFCI nuisance tripping


I find the tamper resistant outlets ridiculous for use in ALL areas of the home. I can understand living room, bedroom areas where the outlets are closer to the ground, but areas not easily accesible like behind the fridge or over the range microwave, behind the stove, above counter tops should be allowed to be standard receptacles. The GFCI outlets are expensive to start with (compared to a standard duplex outlet) and now the Tamper resistant ones are even more expensive!
theatretch85 is offline   Reply With Quote
Old 04-30-2009, 12:08 PM   #6
My License Ain't 4 Sale..
 
Join Date: Feb 2008
Location: Atlanta, Ga/Hamilton, Al
Posts: 1,813
Default

GFCI nuisance tripping


They make a tool to prevent just this type of nuisance tripping:
Attached Images
File Type: bmp belt.bmp (84.2 KB, 62 views)
InPhase277 is offline   Reply With Quote
Old 04-30-2009, 12:34 PM   #7
Tool Geek
 
PaliBob's Avatar
 
Join Date: Jun 2008
Location: Pacific Palisades CA
Posts: 2,502
Default

GFCI nuisance tripping


Quote:
Originally Posted by Bigplanz View Post
The tamper resistance they are referring to is a shutter system that won't allow a child (or anyone) to put a paper clip/screwdriver/whatever in the hot slot of a receptacle.
I'm well aware of the TR situation. My point was that that for GFCI's the term TR definitely does not refer to the tampering seen by the O.P.
__________________
Disclaimer
& Stay Safe
.....Bob Lavery
PaliBob is offline   Reply With Quote
Old 04-30-2009, 03:51 PM   #8
Member
 
Bigplanz's Avatar
 
Join Date: Apr 2009
Location: Louisville KY
Posts: 516
Default

GFCI nuisance tripping


Quote:
Originally Posted by PaliBob View Post
I'm well aware of the TR situation. My point was that that for GFCI's the term TR definitely does not refer to the tampering seen by the O.P.
Well, she wasn't exactly tampering with it by pushing the test button. At 2, she was just doing what toddlers do: investigating her world. We have started firmly saying: "NO!" when she tries to push it now. She covers her eyes, cries and runs across the room. It's very dramatic.

Not sure how much more expensive a new house would be with TR receptacles, GFCI and AFCI breakers, as per the 2008 NEC. Let's see.... let's say there are 50 receptacles in a three bedroom house. At $2 a piece (I saw them at Lowes for this) that would be $100. Even if they were $5 a piece that would be only $250. My house has five GFCI in it right now. Let's say a new house (and garage) needed 15. That's about $200, tops.

Say you need 20 AFCI breakers. According to a quick search of Amazon (probably not the lowest price you could find) they go for between 35 and 55 bucks a piece. Lets say the average is 45 bucks. That puts 20 breakers at about $900. So $1400 tops? For a 200K house? Not a really high price or percentage of the total house costs.

Last edited by Bigplanz; 04-30-2009 at 03:56 PM.
Bigplanz is offline   Reply With Quote
Old 04-30-2009, 09:06 PM   #9
My License Ain't 4 Sale..
 
Join Date: Feb 2008
Location: Atlanta, Ga/Hamilton, Al
Posts: 1,813
Default

GFCI nuisance tripping


You can pick up a belt a walmart for like $5.
InPhase277 is offline   Reply With Quote
Old 04-30-2009, 09:12 PM   #10
Learning by Doing
 
Leah Frances's Avatar
 
Join Date: Jan 2008
Location: Easton, Maryland
Posts: 3,156
Blog Entries: 7
Default

GFCI nuisance tripping


This made me really laugh - I was so ready for another GFCIs-are-the-devil rant.
__________________
If I could only remember to THINK about what I was doing before I did it.
Leah Frances is offline   Reply With Quote
Old 04-30-2009, 09:46 PM   #11
Member
 
Bigplanz's Avatar
 
Join Date: Apr 2009
Location: Louisville KY
Posts: 516
Default

GFCI nuisance tripping


Quote:
Originally Posted by Leah Frances View Post
This made me really laugh - I was so ready for another GFCIs-are-the-devil rant.
I personally have never had a problem with GFCI's tripping inappropriately. I have two in the garage (don't want to lose all my power if one trips, so I have isolated part of the circuit. One trips and it doesn't bring everything down and the lights are isolated on a non-GFCI part of the circuit so they won't go down at all).

Anyway, I have run all kind of power tools, including angle grinders, jig saws, circular saws (both 20+ years old) and have never had a problem. Ran a 16 hp shopvac on the end of a 125 feet of 12 gauge extension cord. No problem. The only thing that ever tripped my garage GFCI was a 6 inch, clip on fan rated at 0.6A. Funny.

Oh, I have blank face plates on her receptacles in her room, and safety plugs everywhere else she has access to. She has never shown any interest in a plug but the GFCI has a little glow light to indicate it's 'on' so she must zero in on that when she goes down to the basement.

Bigplanz is offline   Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Freezer tripping GFCI davidclements Appliances 57 08-13-2014 08:14 PM
New GFCI Breaker Tripping w/ 3-way Flourescents BigJimmy Electrical 8 12-29-2008 02:29 PM
GFCI intermittent nuisance trips jejm1975 Electrical 43 09-07-2008 09:18 AM
20 Amp Breaker tripping with GFCI panhandlion Electrical 7 12-12-2007 08:59 PM




Top of Page | View New Posts

Copyright © 2003-2014 Escalate Media. All Rights Reserved.