Distance between the main breaker panel and a manual transfer switch panel


It's hurricane season, and I want to be better prepared than I have in the past. I have a small portable generator (Duramax XP4400E, 3600 watts), that meets our needs (fridge, room AC, a few lamps, and one small LCD TV).

In years past, I have run a bunch of cords from the generator in the backyard all over the house, but don't want to do it any more.

So I bought a small six circuit manual transfer switch (Reliance Controls 30416A) that can take the feed from the generator (240V, 3P, 4W), and feed to the appropriate 120V circuits.

My main breaker panel is inside the house, and it would be very convenient to mount the transfer switch just one stud over. This means the conduit between the transfer switch is only about 4-5 inches long, and the flush mounts for the two panels are about an inch apart.

Is that a code violation? Can the two panels be so close together? Reliance Controls support personnel say it is not a national code violation.

I'm in Jefferson Parish, Louisiana - anyone know if it is a violation here? Or anywhere else.

Thanks!
Jerry Sr.

jerryallie is offline   Reply With Quote
Join DIYChatroom.com

Join the #1 DIY Forum Today - It's Totally Free!

DIYChatroom.com - Are you about to start a new home improvement task and need some help? Do you need advise on what products to buy? Or maybe you can give others some advice? No matter where you fit in you'll find that DIY Chatroom is a great community to join. Best of all it's totally free.

Join DIYChatroom.com - Click Here
JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. DIYChatroom.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any home improvement task!
Old 09-01-2010, 05:40 PM   #2
Electrical Contractor
 
Join Date: Jun 2004
Location: Newnan GA
Posts: 5,004
Default

Distance between the main breaker panel and a manual transfer switch panel


Not a violation I am aware of!

__________________
Yes I am a Pirate, 200 years too late. "Jimmy Buffett"
jbfan is offline   Reply With Quote
Old 09-01-2010, 09:11 PM   #3
" Euro " electrician
 
frenchelectrican's Avatar
 
Join Date: Apr 2006
Location: WI & France { in France for now }
Posts: 4,947
Default

Distance between the main breaker panel and a manual transfer switch panel


Nope.,

Ya good to go as long it is after the main breaker and I know many manual transfer switch are good set up.

But a nice gotcha is make sure you isolated the netural et grounding if you run thru the transfer swtich { you will have to treat them like subpanel anyway }

Merci.
Marc
frenchelectrican is offline   Reply With Quote
Reply

Tags
generator, main panel, transfer panel


-->
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Choosing a manual transfer swtich for 7500 w generator homerb Electrical 11 07-24-2012 01:15 AM
Manual transfer switch to power an existing sub-panel joestewart Electrical 10 11-23-2009 03:30 PM
Adding a Sub Panel for Transfer Switch dcopps Electrical 27 08-24-2009 11:36 AM
This doesnt seem right. JoulesWinfield Electrical 27 07-26-2009 08:40 PM
Transfer switch to main panel connection i6pwr Electrical 3 01-28-2009 07:09 AM


Top of Page | View New Posts


All times are GMT -4. The time now is 11:35 PM.


© 2003 - 2010 The Building Network LLC