york upright oil furnace with direct drive blower motor


i just installed a yorkoil furnace in my house. when i went to fire it up last night everything went beautiful except the blower motor.it first overloaded and shut it off then i freed it up but then it made alot of racket. i messed with it for a while and now i am to the point where it is good while running but very very noisy when starting and slowing to a stop. any suggestions on how i can resolve this.. thanks.

bigbruce is offline   Reply With Quote
Old 10-16-2010, 08:39 AM   #2
Hvac Pro
 
Join Date: Nov 2008
Location: Winnipeg, Canada
Posts: 9,417
Rewards Points: 38
Default

york upright oil furnace with direct drive blower motor


Make sure the blower wheel is not hitting the cowling or off balance or has a loose hub or fins. Then replace the motor.

__________________
"Cut it twice and it is still too short".
yuri is offline   Reply With Quote
Old 10-16-2010, 09:03 AM   #3
Newbie
 
Join Date: Oct 2010
Posts: 5
Rewards Points: 0
Default

york upright oil furnace with direct drive blower motor


its brand new furnace.is it possible the motor is bad? its all new.
bigbruce is offline   Reply With Quote
Old 10-16-2010, 09:18 AM   #4
fabrk8r
 
fabrk8r's Avatar
 
Join Date: Feb 2010
Location: Iowa
Posts: 849
Rewards Points: 0
Default

york upright oil furnace with direct drive blower motor


Some times blower wheel set screws are not tight when the unit is shipped from the factory. It's one of the first things to check when installing equipment. If it turns out that the blower wheel set screws are tight, check to make sure there is nothing in the blower, such as factory paperwork or styrofoam packing.
__________________
"The physician can bury his mistakes, but the architect can only advise his clients to plant vines." -- Frank Lloyd Wright
fabrk8r is offline   Reply With Quote
Old 10-16-2010, 09:21 AM   #5
Hvac Pro
 
Join Date: Nov 2008
Location: Winnipeg, Canada
Posts: 9,417
Rewards Points: 38
Default

york upright oil furnace with direct drive blower motor


it first overloaded and shut it off then i freed it up (how did you free it up) i messed with it for a while (what exactly did you do when messing with it)


__________________
"Cut it twice and it is still too short".
yuri is offline   Reply With Quote
Old 10-16-2010, 10:05 AM   #6
Newbie
 
Join Date: Oct 2010
Posts: 5
Rewards Points: 0
Default

york upright oil furnace with direct drive blower motor


ok i will check the set screws and stuff. i freed it up by spinning it with my hand as it was trying to start.and i messed with it by turning the hex nuts that hold it on cowl where the rubber bushings are . i can spin it by hand for 3/4 of the way around with it totally quiet then it scrapes the other 1/4 of the way.
bigbruce is offline   Reply With Quote
Old 10-16-2010, 10:08 AM   #7
Newbie
 
Join Date: Oct 2010
Posts: 5
Rewards Points: 0
Default

york upright oil furnace with direct drive blower motor


i think i might just take it out and check it over. is it just the 2 screws on each side on the rail that i take out to get it out.or is there an easier way
bigbruce is offline   Reply With Quote
Old 10-16-2010, 10:47 AM   #8
Hvac Pro
 
Join Date: Nov 2008
Location: Winnipeg, Canada
Posts: 9,417
Rewards Points: 38
Default

york upright oil furnace with direct drive blower motor


Cannot see it from here. Sounds like the blower wheel is too far towards the cowling and hitting it and needs to be reset on the motor shaft so it is closer to the motor. Turning those hex nuts just squeezed the rubber mounts in and gave it more clearance. I have had new blower wheels be badly off balance or warped. Take it out and spin it and see how much side to side motion/play it has. Should be less than a 1/2 inch.
__________________
"Cut it twice and it is still too short".
yuri is offline   Reply With Quote
Old 10-16-2010, 10:58 AM   #9
An old Tradesmen
 
Join Date: Oct 2008
Location: PA
Posts: 25,080
Rewards Points: 52
Default

york upright oil furnace with direct drive blower motor


Over the years. I got more then one furnace from York/UPG that had a banged up blower housing, or imbalanced wheel. So yes, its possible its a bad wheel or housing from the factory.

My definition of a factory: 300 people waiting for quitting time.
beenthere is online now   Reply With Quote
Old 10-16-2010, 11:17 AM   #10
Hvac Pro
 
Join Date: Nov 2008
Location: Winnipeg, Canada
Posts: 9,417
Rewards Points: 38
Default

york upright oil furnace with direct drive blower motor


And then there is quality issues and how sturdy the blower wheel is and thickness of fan housing. People who think all furnaces are the same need to pull a blower wheel and fan out of 6-8 brands and then you will see where the quality gets cut and why you get what you pay for.
__________________
"Cut it twice and it is still too short".
yuri is offline   Reply With Quote
Old 10-16-2010, 02:07 PM   #11
Newbie
 
Join Date: Oct 2010
Posts: 5
Rewards Points: 0
Default

york upright oil furnace with direct drive blower motor


thanks for everyones input. it ended up being i just had to loosen the set screw and slide it on the shaft to line it up. again. thank you guys

bigbruce is offline   Reply With Quote
Reply

Tags
furnace blower, furnace fan, furnace repair help


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Blower motor help playdoe HVAC 9 09-16-2010 04:26 PM
Blower motor in old bryant furnace runs constantly GetYourShineBox HVAC 2 07-20-2010 07:49 PM
A/C Blower Motor Seems Slow PillMD HVAC 5 04-01-2010 08:17 AM
Problems with new furnace..Overheating, having to reset. Furnace too big? Tommy2 HVAC 41 12-01-2008 01:55 PM
Furnace blower motor noise rivershorereid HVAC 1 10-04-2008 02:31 PM




Top of Page | View New Posts

Copyright © 2003-2014 Escalate Media. All Rights Reserved.