stevem447 07-12-2012 06:10 PM

TRANE XE 80 Status LED Question
 
Hello all,

I have a Trane XE 80 Model TUD080C936H4, The blower motor went this week, I replaced the blower motor and the run capacitor. The unit comes on and appears to be running OK, however the White and Rogers control board (50A50 473) has a steady blinking light, the status codes are not listed on the unit, before I buy a new controller I'd like to find out if this code is normal or if there is an issue. I stopped the unit and checked the new motor and it is a bit hot, but the board is not hot and I do not smell anything burning, as I did with the old motor I replaced. Any feed back would be greatly appreciated. Thanks

Done That 07-13-2012 07:05 AM

Steady "slow" blink = Normal operation , no call for operation present.
Steady "fast" blink = Normal operation, call present.
Solid on is a control board fault.
2/3/4/5 flashes are specific fault codes.

stevem447 07-13-2012 07:07 AM

Quote:

Originally Posted by Done That (Post 964647)
Steady "slow" blink = Normal operation , no call for operation present.
Steady "fast" blink = Normal operation, call present.
Solid on is a control board fault.
2/3/4/5 flashes are specific fault codes.


Awesome Thanks!