proper venting install[plastic]


OK, first time asking ,
90% furnace one story home exhaust[plastic] runs out of furnace down to crawspace [under floor and furnace] and out side of home.
we good with this or would there be a back pressure?
no manufacturer instuctions, Thanks

gasmanohio is offline   Reply With Quote
Join DIYChatroom.com

Join the #1 DIY Forum Today - It's Totally Free!

DIYChatroom.com - Are you about to start a new home improvement task and need some help? Do you need advise on what products to buy? Or maybe you can give others some advice? No matter where you fit in you'll find that DIY Chatroom is a great community to join. Best of all it's totally free.

Join DIYChatroom.com - Click Here
JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. DIYChatroom.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any home improvement task!
Old 10-23-2012, 11:17 PM   #2
Member
 
Join Date: May 2010
Location: winnipeg manitoba canada
Posts: 685
Default

proper venting install[plastic]


Quote:
Originally Posted by gasmanohio View Post
OK, first time asking ,
90% furnace one story home exhaust[plastic] runs out of furnace down to crawspace [under floor and furnace] and out side of home.
we good with this or would there be a back pressure?
no manufacturer instuctions, Thanks
what brand of furnace....few can be vented down.....

carmon is offline   Reply With Quote
The Following User Says Thank You to carmon For This Useful Post:
gasmanohio (10-25-2012)
Old 10-23-2012, 11:23 PM   #3
Member
 
Join Date: Oct 2011
Location: pa
Posts: 3,176
Default

proper venting install[plastic]


can you get us a picture of this gem....
ben's plumbing is online now   Reply With Quote
Old 10-24-2012, 10:09 AM   #4
Newbie
 
Join Date: Oct 2012
Location: ohio
Posts: 3
Default

proper venting install[plastic]


Thanks for the reply's, no picture and will ask about brand name, I got a phone call about this and I'm just trying to put facts to it, i'm looking for a book with some help, National fuel gas. has exit terminals of mechanical draft/direct vent , 12 inch minimum,from grade, thats all I can find at this time, THANKS AGAIN
gasmanohio is offline   Reply With Quote
Old 10-24-2012, 03:25 PM   #5
An old Tradesmen
 
Join Date: Oct 2008
Location: PA
Posts: 18,627
Default

proper venting install[plastic]


Trane allows the vent to run down. Has special instructions for it. But only applies to Trane. Other brands may not have approval.
beenthere is offline   Reply With Quote
The Following User Says Thank You to beenthere For This Useful Post:
gasmanohio (10-25-2012)
Old 10-25-2012, 05:14 PM   #6
Newbie
 
Join Date: Oct 2012
Location: ohio
Posts: 3
Default

proper venting install[plastic]


sorry no picture or brand name ,

gasmanohio is offline   Reply With Quote
Reply


-->
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Proper venting of new roof on attached garage jlatulippe Roofing 1 11-26-2009 04:24 PM
Too Much Soffit Venting? atw58 Roofing 2 05-16-2009 09:19 AM
Could lack of soffit venting increase indoor negative air pressure? creamaster Roofing 1 03-07-2009 02:27 PM
Soffit venting vs. DCI Smart Vent JDPII Roofing 1 02-28-2009 09:42 PM
Venting basement bathroom fixtures ccathy247 Plumbing 1 11-01-2008 04:44 PM


Top of Page | View New Posts


All times are GMT -4. The time now is 03:37 PM.


© 2003 - 2010 The Building Network LLC