payne furnace inducer motor


Hello all, I am new here officially, but after searching these forums for the last two days, I feel as though I know you all already! LOL. Not to mention, you all deserve teaching degrees with the amount of info I have learned about my furnace from you in the last two days. So here is the situation:

I have a Payne furnace. Ive been getting code 31 (pressure switch issues). From what I have learned on here, I have been able to deduce it is the inducer motor. When restarting the furnace, it would kick on for the 90 second trial and then shut off. I would hear a slight "squeal" behind the inducer fan and noticed that it "tried" to rotate, but wouldnt. At one point I spun it by hand, it caught, and the furnace ran for about an hour or so (although it was making some extra noise from that fan). It then kicked back off, and wont even jump start by turning that fan. I priced inducer motors this morning they are expensive. Does it sound like I need a brand new motor or is there a chance that it can be manipulated into working? Either way, is it something I can take off on my own or is this going to take a "professional" fix? I really want to prove my wife wrong on this one, so any help is GREATLY appreciated.

The part number in question hc21z123a

Let me know if you need any more info. Thanks!

Advertisement

minime_moomey is offline   Reply With Quote
Old 02-18-2010, 06:51 PM   #2
Hvac Pro
 
Join Date: Nov 2008
Location: Winnipeg, Canada
Posts: 10,113
Rewards Points: 864
Default

payne furnace inducer motor


Post the model # of the furnace and serial # and a pic of the inducer motor and furnace with doors off.

Advertisement

__________________
"Cut it twice and it is still too short".
yuri is offline   Reply With Quote
Old 02-18-2010, 07:37 PM   #3
Newbie
 
Join Date: Feb 2010
Posts: 4
Rewards Points: 10
Default

payne furnace inducer motor


Model# pgm8aa060155
Serial#2103A25998

Sorry, this would have been helpful earlier! The cold must be getting to my brain.
Attached Thumbnails
payne furnace inducer motor-picresized_th_204619423987b60da6e6853c52baeb6c.jpg  
minime_moomey is offline   Reply With Quote
Old 02-18-2010, 07:48 PM   #4
Hvac Pro
 
Join Date: Nov 2008
Location: Winnipeg, Canada
Posts: 10,113
Rewards Points: 864
Default

payne furnace inducer motor


Payne/Carrier parts are EXPENSIVE and that unit needs replacing, cannot be manipulated. Not easy to replace as you need to replace the motor AND the wheel in the fan. The wheel bends VERY easily and gets off balance. I would recommend a Payne or Carrier or Bryant (Carrier owns all 3 of them)dealer as that way if it vibrates/gets noisy etc you have a warranty and they have to make it work. I have changed a couple dozen of them and it is not that easy. First time is always the worst. Get them to clean and show you the flame sensor. Needs cleaning once a year. Is it damp in the furnace area? looks rusty to me. Dampness will shorten the life of the circuit board etc so a de-humidifier is recommended.
__________________
"Cut it twice and it is still too short".

Last edited by yuri; 02-18-2010 at 07:52 PM.
yuri is offline   Reply With Quote
Old 02-18-2010, 09:31 PM   #5
An old Tradesmen
 
Join Date: Oct 2008
Location: PA
Posts: 26,533
Rewards Points: 4,704
Default

payne furnace inducer motor


PITA inducer.

If your brave. And don't mind the wife saying I told you so if you damage the new wheel. Try it.
beenthere is online now   Reply With Quote
Old 02-18-2010, 09:37 PM   #6
Hvac Pro
 
Join Date: Nov 2008
Location: Winnipeg, Canada
Posts: 10,113
Rewards Points: 864
Default

payne furnace inducer motor


PITA furnace. All those 34" Rheems and Carriers are a "Payne" to work on. LOL. Takes 2-3 hrs to change a fan motor on a Rheem high, by the time you disconnect all the plumbing etc and fix the leaks later.
__________________
"Cut it twice and it is still too short".
yuri is offline   Reply With Quote
Old 02-19-2010, 06:39 AM   #7
Newbie
 
Join Date: Feb 2010
Posts: 4
Rewards Points: 10
Default

payne furnace inducer motor


Thanks for the help guys. Time to bite the bullet and get one ordered.
minime_moomey is offline   Reply With Quote
Old 02-19-2010, 10:57 PM   #8
retired elect/hvac/plumb
 
plummen's Avatar
 
Join Date: Jan 2010
Location: south east of omaha/The island of misfit contractors
Posts: 2,916
Rewards Points: 2,010
Default

payne furnace inducer motor


did you pull the housing off and check for birds trapped in there? i think my record is 5-6 in one inducer motor
plummen is offline   Reply With Quote
Old 02-20-2010, 08:10 AM   #9
Newbie
 
Join Date: Feb 2010
Posts: 4
Rewards Points: 10
Default

payne furnace inducer motor


Quote:
Originally Posted by plummen View Post
did you pull the housing off and check for birds trapped in there? i think my record is 5-6 in one inducer motor
5-6 in ONE?!?! LOL. That is impressive. Now Im going to ask a question in fear of getting flamed, but what do you mean by the "housing"? Are you talking like the main front part that the inducer motor is connected to or something else? I have time to mess with it today, so I can definately give it a shot.
minime_moomey is offline   Reply With Quote
Old 02-20-2010, 01:25 PM   #10
retired elect/hvac/plumb
 
plummen's Avatar
 
Join Date: Jan 2010
Location: south east of omaha/The island of misfit contractors
Posts: 2,916
Rewards Points: 2,010
Default

payne furnace inducer motor


the housing unbolts from front of furnace and flue pipe.Itscommon around here for birds to sit on top of open chimneys to warm up,but sometimes the flue gas basically knocks them out causing them to drop into chimney.
Anyway sometimes they wake up in bottem of chimney and get disoriented trying to get out and end in the inducer motor. worst thing i ever saw was a full size duck stuck in a chimney of a house by elkhorn river,went to pull the single wall pipe out of the side of brick chimney and came face to face with charbroiled face of duck! scared the hell out of me to say the least!
plummen is offline   Reply With Quote
Old 02-20-2010, 01:29 PM   #11
Hvac Pro
 
Join Date: Nov 2008
Location: Winnipeg, Canada
Posts: 10,113
Rewards Points: 864
Default

payne furnace inducer motor


I had a red squirrel do a kamikaze routine in a 8" clay tile lined chimney. Down the chimney into the vent pipe. Had to pull it out with needle nose pliers, not fun!
__________________
"Cut it twice and it is still too short".
yuri is offline   Reply With Quote
Old 02-20-2010, 01:35 PM   #12
Member
 
Join Date: Oct 2009
Location: Nebraska
Posts: 2,362
Rewards Points: 1,000
Default

payne furnace inducer motor


Think my favorite one was a squirrel. Husband started laughing because his wife fed the rodents and this one was so fat it got stuck in a 4" flue. Inducer ran just fine but the pressure switch sure wouldn't close.
Marty S. is offline   Reply With Quote
Old 02-20-2010, 01:46 PM   #13
Hvac Pro
 
Join Date: Nov 2008
Location: Winnipeg, Canada
Posts: 10,113
Rewards Points: 864
Default

payne furnace inducer motor


Had a guy complain or poor airflow/furnace overheating. Buddy was not to impressed when I handed him a $95 bill to remove the plastic wrapper from his spankin new air filter. Don't imagine he told his wife the "truth".
__________________
"Cut it twice and it is still too short".
yuri is offline   Reply With Quote
Old 02-20-2010, 01:52 PM   #14
retired elect/hvac/plumb
 
plummen's Avatar
 
Join Date: Jan 2010
Location: south east of omaha/The island of misfit contractors
Posts: 2,916
Rewards Points: 2,010
Default

payne furnace inducer motor


now thats funny,i dont care who ya is!

Advertisement

plummen is offline   Reply With Quote
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Water Inside/Around American Standard Furnace michrob HVAC 8 12-08-2011 04:51 PM
How do I turn off the inducer motor on my gas furnace rj2001xl HVAC 3 12-02-2011 08:43 PM
Carrier Model 58MVP inducer motor deanray HVAC 11 11-19-2010 05:33 PM
Inducer motor or control circuit? Please help me troubleshoot. averagerob HVAC 1 03-03-2009 02:43 PM
Loud furnace -- Inducer Valve or Motor Bad? buhockey21 HVAC 2 02-04-2009 07:09 AM




Top of Page | View New Posts