Join Date: Sep 2006
Posts: 8
|
Help TRANE XE-80 furnace
I have a TRANE XE-80 furnace.
During general maintenance I accidentally broke the reverse flow switch on my blower assembly. I've ordered and received a replacement switch. For reference, the switch is TRANE part #SWT1696. This switch attaches to the blower assembly which is TRANE part #BLW00551. The description of this switch is "Switch; Reverse Flow, Open at 140F, Close at 125, 1/2 In" The part that I have to replace is #11 on this diagram. http://americanhvacparts.com/Merchan.../blw005533.jpg There are 2 yellow wires that come out of the motor assembly and there are 2 places on the reverse flow switch to connect these wires. My question is, does it matter what yellow wire goes where on this switch ? -S |
|
|
|
|
|
#2 |
|
World famous jerk.
Join Date: Dec 2005
Location: central PA
Posts: 440
|
Help TRANE XE-80 furnace
No, it does not matter at all. It's just making and breaking. There is no "line" and "load" per se.
|
|
|
|
|
|
#3 |
|
Newbie
Join Date: Sep 2006
Posts: 8
|
Help TRANE XE-80 furnace
Are you sure ? It looks like the wiring diagram shows that there is a difference between the two terminals.
I've scanned the wiring diagram below. Look at the bottom to see the reverse flow switch. You can clearly see that it is marked 3 and 5 and each goes to a different place. Also the switch it self looks like it has some sort of polarity. Again, my switch only has a 1 and a 3 on it, there is no marking of a 5. http://suprfile.com/get.php?id=3mv4x7v Last edited by squeed; 10-08-2006 at 08:49 AM. |
|
|
|
|
|
#4 |
|
World famous jerk.
Join Date: Dec 2005
Location: central PA
Posts: 440
|
Help TRANE XE-80 furnace |
|
|
|
|
|
#5 |
|
Member
Join Date: Mar 2006
Posts: 2,083
|
Help TRANE XE-80 furnace
How many volts are going to the switch and how many volts are coming out of the switch after it is open?
|
|
|
|
|
|
#6 |
|
Newbie
Join Date: Sep 2006
Posts: 8
|
Help TRANE XE-80 furnace
mdshunk, No slap intended. I just wanted to make sure, it took 3 weeks to get this switch and I don't want to blow it out, especially since it is getting cold and I need to install it to use the heat.
Regarding redline's question. On the package it says this. "Switch; Reverse Flow, Open 140F, Close 130F, 3/4 In., 120/240V" So I think the answer is 120 in 240 out ? -S |
|
|
|
|
|
#7 |
|
I blame ProWallGuy
Join Date: Sep 2006
Posts: 244
|
Help TRANE XE-80 furnace
|
|
|
|
|
|
#8 |
|
World famous jerk.
Join Date: Dec 2005
Location: central PA
Posts: 440
|
Help TRANE XE-80 furnace |
|
|
|
|
|
#9 |
|
Newbie
Join Date: Sep 2006
Posts: 8
|
Help TRANE XE-80 furnace
Guys, I belong to a lot of forums and you never know who knows what they are talking about and who is just blowing hot air. As you can see from the number of my posts here, I'm new to this forum.
I didn't know that there were professionals who frequent this board to give advice. For a layman who doesn't know anything about HVAC, looking at a bunch of wires hooked into something that makes fire in your house is concerning. So I don't think that you can blame a guy for just wanting to be sure. -S |
|
|
|
|
|
#10 |
|
Member
Join Date: Apr 2006
Location: jersey
Posts: 135
|
Help TRANE XE-80 furnace
squeed ,you got the answer to the question many moons ago. for free.if you continue to ask the question then it seems to me you have no clue as to what you are doing. call a pro befor you get hurt.winters coming.
|
|
|
|
|
|
#11 | |
|
registered
Join Date: Feb 2005
Location: Illinois (kankakee county)
Posts: 976
|
Help TRANE XE-80 furnaceQuote:
|
|
|
|
|
|
|
#12 | |
|
Newbie
Join Date: Oct 2006
Posts: 1
|
Help TRANE XE-80 furnaceQuote:
Keep at it. |
|
|
|
|
|
|
#13 | |
|
World famous jerk.
Join Date: Dec 2005
Location: central PA
Posts: 440
|
Help TRANE XE-80 furnaceQuote:
|
|
|
|
|
![]() |
| Thread Tools | Search this Thread |
| Display Modes | |
|
|
Similar Threads
|
||||
| Thread | Thread Starter | Forum | Replies | Last Post |
| Heil Furnace Burner Problem | timothyr | HVAC | 78 | 01-18-2013 07:49 PM |
| TRANE XE-80 furnace on OVERDRIVE Help ! | squeed | HVAC | 6 | 07-15-2007 06:25 PM |
| Trane XE 90 Furnace | Masterdrafter | HVAC | 1 | 02-01-2007 06:54 PM |
| trane furnace with inducer blower error | tjh57 | HVAC | 1 | 10-22-2006 08:45 PM |