Northland101 11-28-2008 10:27 AM

Furnace installed. Intake from outside. DO i need it?
 
I recently had a furnace installed. The salesman said he would have them put in an intake from the outside because there wasn't one. It's an 80% efficient furnace, older home, but the mechanical room is semi enclosed in its own room. When the salesman was selling me the unit, he said 'these older homes like yours breathe good on their own and probably don't need an intake from outside, but we will put one in anyways'. It is on the service order when he sold me the unit, but when they installed the furnace i guess he said it would be too hard to put in. I told him okay and now i am rethinking it and might have him put the intake vent pipe in from outside.

hvaclover 11-28-2008 10:36 AM

Should have gone 905, but that's water under the bridge now.

If the mechanical room is with a door that you keep closed, then a combustion air vent is necessary. If on the other hand there is no door and the basement area it draws air from to burn, then it won't be needed.

hvaclover 11-28-2008 10:37 AM

Should have gone 90%, but that's water under the bridge now.

If the mechanical room has a door that you keep closed, then a combustion air vent is necessary. If on the other hand there is no door and the basement area it draws air from to burn, then it won't be needed.

Northland101 11-28-2008 10:46 AM

slight door.
 
the room has 3 plastic like folding doors on 3 of the 4 sides of the room. Another wall has no door. And there is a little gap on the bottom of the doors

hvaclover 11-28-2008 11:21 AM

Quote:

Originally Posted by Northland101 (Post 191057)
the room has 3 plastic like folding doors on 3 of the 4 sides of the room. Another wall has no door. And there is a little gap on the bottom of the doors

Unless the Bi-fold doors are ALL louvered, then you need the combustion air duct.

tk03 11-28-2008 02:03 PM

This is a calculation for combustion air. You can calculate it yourself to determine the need of or not.
http://www.comfort-calc.net/Combusti...lculation.html