Old 06-20-2009, 06:03 PM   #1
Newbie
 
Join Date: Jun 2009
Location: AZ
Posts: 23
Rewards Points: 10
Question

Duct and reducers


Hi new to the site and have a question.

I did a complete room by room manual J My trunk will be strait
one trunk line is 12 foot the other is 36 foot long should there be any
reducers as the trunk nears the end? Or somewhere in the middle?

Thanks in advance.

Advertisement

Dominick is offline   Reply With Quote
Old 06-20-2009, 09:56 PM   #2
Member
 
Join Date: Dec 2008
Location: Dayton Ohio Area
Posts: 670
Rewards Points: 500
Default

Duct and reducers


For the 36; long run, yes. Location depends on where the takeoffs are and what size they are.

The 12' run I think would be fine.

Advertisement

__________________
-Andrew
DIY hobbiest
AndrewF is offline   Reply With Quote
Old 06-20-2009, 10:22 PM   #3
An old Tradesmen
 
Join Date: Oct 2008
Location: PA
Posts: 26,465
Rewards Points: 4,576
Default

Duct and reducers


Reduce when ever the velocity drops too low.
Too low varies with what velocity you had at teh first piece of trunk line.

The 12' section may need to be reduced, depending on how much air, the first supplies on it take. The more air they take, the lower your velocity will be.
beenthere is offline   Reply With Quote
Old 06-21-2009, 02:14 AM   #4
Newbie
 
Join Date: Jun 2009
Location: AZ
Posts: 23
Rewards Points: 10
Default

Duct and reducers


Ok cool that's understandable.

Tho one thing that intrigues me is a some of my rooms (example) 13 x 11 and a ceiling height of 7' 3" called out 2 5inch round ducts I would have thought it would have called for 2 6inch 2 windows in the room one on east wall and one on north. Two 5inch sound right?

Room came out to be a heat gain of 4,077.

Thanks again.
Dominick is offline   Reply With Quote
Old 06-21-2009, 07:20 AM   #5
An old Tradesmen
 
Join Date: Oct 2008
Location: PA
Posts: 26,465
Rewards Points: 4,576
Default

Duct and reducers


5" is queationable.

What CFM did it say.
What static pressue?
And what are you using, hard pipe or flex?

5" flex is equivelant to 4" hard pipe.
beenthere is offline   Reply With Quote
Old 06-21-2009, 02:55 PM   #6
Newbie
 
Join Date: Jun 2009
Location: AZ
Posts: 23
Rewards Points: 10
Default

Duct and reducers


The air handler puts out about 1200 cfm.

Calc for that room was 173 cfm

Its going to be hard pipe trying to stay away from flex.
Now the speed of air shows a recommended 900 but I thought it was supposed to be 600?
Dominick is offline   Reply With Quote
Old 06-21-2009, 04:56 PM   #7
An old Tradesmen
 
Join Date: Oct 2008
Location: PA
Posts: 26,465
Rewards Points: 4,576
Default

Duct and reducers


Your not going to get 173 out of 2-5" supplies too easiliy.
It will be loud.

Either needs to be 1-7" and a 5", or 2-6".
beenthere is offline   Reply With Quote
Old 06-21-2009, 05:31 PM   #8
Newbie
 
Join Date: Jun 2009
Location: AZ
Posts: 23
Rewards Points: 10
Default

Duct and reducers


Quote:
Originally Posted by beenthere View Post
Your not going to get 173 out of 2-5" supplies too easiliy.
It will be loud.

Either needs to be 1-7" and a 5", or 2-6".
Had a feeling it was 2-6" 2-5"s just did not look right

And no matter what ill be using dampers like normal Thanks.
Dominick is offline   Reply With Quote
Old 06-21-2009, 05:33 PM   #9
Newbie
 
Join Date: Jun 2009
Location: AZ
Posts: 23
Rewards Points: 10
Default

Duct and reducers


You have an e-mail I could send you a PDF of the load calcs?
Dominick is offline   Reply With Quote
Old 06-21-2009, 05:41 PM   #10
An old Tradesmen
 
Join Date: Oct 2008
Location: PA
Posts: 26,465
Rewards Points: 4,576
Default

Duct and reducers


You can't recieve PMs yet.

I was going ot PM it to you.
beenthere is offline   Reply With Quote
Old 06-21-2009, 05:47 PM   #11
Newbie
 
Join Date: Jun 2009
Location: AZ
Posts: 23
Rewards Points: 10
Default

Duct and reducers


yeah i noticed lol and I dont know how many posts i need before i can PM

mine is

k1518n69 AT hotmail dot com

sorry about the goofy way i did it trying to make it so spam bots cant recognize it
Dominick is offline   Reply With Quote
Old 06-22-2009, 06:23 AM   #12
An old Tradesmen
 
Join Date: Oct 2008
Location: PA
Posts: 26,465
Rewards Points: 4,576
Default

Duct and reducers


Keep getting delivery notifications when I email you.
beenthere is offline   Reply With Quote
Old 06-22-2009, 03:54 PM   #13
Newbie
 
Join Date: Jun 2009
Location: AZ
Posts: 23
Rewards Points: 10
Default

Duct and reducers


Do not know why I got 2 emails from you and did reply

Thanks
Dominick is offline   Reply With Quote
Old 06-22-2009, 04:20 PM   #14
An old Tradesmen
 
Join Date: Oct 2008
Location: PA
Posts: 26,465
Rewards Points: 4,576
Default

Duct and reducers


kept getting non delivery notices.


What size A/C did you select again.

According ot my charts. At your design conditions. You need a 3 ton unit, to meet the cooling load of your sensible load.
And will nee to move 1400CFM.
beenthere is offline   Reply With Quote
Old 06-22-2009, 05:04 PM   #15
Newbie
 
Join Date: Jun 2009
Location: AZ
Posts: 23
Rewards Points: 10
Default

Duct and reducers


I take it you got my email.
And Wow that thing was totally off?

eventually im going to install double pane windows will the 3ton be over sized then?

Advertisement

Dominick is offline   Reply With Quote
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Return Air Vents stubits HVAC 149 04-21-2010 05:50 PM
Reducers, forward and backward Yoyizit HVAC 0 06-07-2009 08:04 PM




Top of Page | View New Posts