lmorsino 06-11-2012 06:15 PM

B-vent supports?
 
Hi, I'm running b-vent for a water heater vertically up a wall cavity from a basement to an attic. Are any straps or supports needed in the wall cavity to secure the vent? And if so, how many for an 8' rise?

beenthere 06-11-2012 07:09 PM

Yes. probably get a way with 2.

ben's plumbing 06-11-2012 08:47 PM

Quote:

Originally Posted by lmorsino (Post 941162)
Hi, I'm running b-vent for a water heater vertically up a wall cavity from a basement to an attic. Are any straps or supports needed in the wall cavity to secure the vent? And if so, how many for an 8' rise?

we support every 2.5 foot on the vertical run... I would use 3 may be alittle over kill but its safe....

COLDIRON 06-12-2012 07:03 AM

They make base supports for B vent that keeps the pipe away from combustibles and holds the pipe in place, that's what you need for support and safety. The base tabs fit into the groves on the pipe.