American Standard 5000 furnace


Furnace works fine for a while but then unexpectedly stops. when checked I get red light blinking 2 times. furnace was bought in 1989-1990.When the power is turned off and back on, it works fine for weeks. it has happened two days in a row this week.

Advertisement

mandtfoster is offline   Reply With Quote
Old 02-07-2014, 09:39 PM   #2
how
Member
 
Join Date: Feb 2011
Location: Vancouver BC
Posts: 1,554
Rewards Points: 624
Default

American Standard 5000 furnace


Somewhere on the furnace will be a legend to show you what those flashes mean.

Advertisement

how is online now   Reply With Quote
Old 02-07-2014, 09:49 PM   #3
Member
 
Join Date: Oct 2011
Location: pa
Posts: 4,645
Rewards Points: 2,604
Default

American Standard 5000 furnace


sounds like flame sensor ....ben sr
ben's plumbing is online now   Reply With Quote
The Following User Says Thank You to ben's plumbing For This Useful Post:
hvactech126 (02-08-2014)
Old 02-07-2014, 09:50 PM   #4
Member
 
Join Date: Jul 2011
Location: Houston Texas
Posts: 1,156
Rewards Points: 650
Default

American Standard 5000 furnace


Sounds like the Hot surface igniter may be bad, found same question on another website and they said tech replaced the hsi.

This is what it looks like http://www.amazon.com/FURNACE-REPLAC.../dp/B0092PZ8S8. Not saying this is yours
__________________
digitalplumber is just a name for use here, I am not a plumber!
digitalplumber is offline   Reply With Quote
Old 02-08-2014, 11:36 AM   #5
AKA HVACTECHFW
 
Join Date: Nov 2010
Location: NE Indiana
Posts: 2,368
Rewards Points: 1,100
Blog Entries: 1
Default

American Standard 5000 furnace


multiple possibilities for "ignition lock out" - flame sensor needs cleaned or the HSI is not getting hot enough to light the gas, or the gas valve is not opening, or the gas if off or there is no gas.
__________________
IT IS WHAT IT IS
hvactech126 is offline   Reply With Quote
The Following User Says Thank You to hvactech126 For This Useful Post:
ben's plumbing (02-08-2014)
Reply


Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
3 - flash code, american standard freedom 90 furnace dfferg HVAC 25 03-05-2012 12:21 AM
Blower problem on American Standard Freedom 90 furnace ekimmo HVAC 8 08-27-2011 10:13 PM
american standard furnace casino1a HVAC 1 08-05-2011 01:36 AM
American Standard Freedom 80 Furnace Jepierson HVAC 1 07-06-2011 06:22 PM
Godman, Lennox, or American Standard homeowner12 HVAC 2 10-13-2009 06:54 AM




Top of Page | View New Posts